| Plan Review Notes For Permit 03100556 |
| Permit Number |
03100556 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-31 00:00:00 | ********* UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE PLANS SUBMITTED, | | | PLANS SHOW TOTAL OF FOUR ELECTRICAL | | | PANELS, TWO 3-PHASE AND TWO SINGLE - | | | PHASE. COPY OF PREVIOUS PERMIT/ELECTRI- | | | -CAL RISER DOES NOT CORRELATE WITH PLANS | | | | | | 2)NOTE:PLANS ARE NOW SHOWING MOST | | | CIRCUITING HOWEVER NO PANEL SCHEDULE(S) | | | WERE SUBMITTED TO CORRELATE? | | | PLEASE ALSO SEE 700.12E FOR EM/EXT LTS | | | CIRCUITING. | | | | | | 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | FOR POSSIBLE EM LTS. PLEASE CLARIFY | | | MIN LTS REQ'D PER LS 101 5-8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|