2003-10-31 00:00:00********* UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS SUBMITTED,
 PLANS SHOW TOTAL OF FOUR ELECTRICAL
 PANELS, TWO 3-PHASE AND TWO SINGLE -
 PHASE. COPY OF PREVIOUS PERMIT/ELECTRI-
 -CAL RISER DOES NOT CORRELATE WITH PLANS
  
 2)NOTE:PLANS ARE NOW SHOWING MOST
 CIRCUITING HOWEVER NO PANEL SCHEDULE(S)
 WERE SUBMITTED TO CORRELATE?
 PLEASE ALSO SEE 700.12E FOR EM/EXT LTS
 CIRCUITING.
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR POSSIBLE EM LTS. PLEASE CLARIFY
 MIN LTS REQ'D PER LS 101 5-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  