2003-10-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03100556
 ADD: 1500 CLARE AVE
 CONT: O/B IVANCEVIC, DANILO
 TEL: (561)493-1975
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; PLEASE INDICATE THE USAGE
 OF EACH AREA. WILL THE LARGER AREA BE US
 ED FOR INDUSTRIAL, FACTORY OR STORAGE?
 IF STORAGE WHAT TYPE OF MATERIALS WILL
 BE STORED THERE?
 2) STORAGE INDICATE (2) MEANS OF EGRESS,
 MUST BE SWING DOORS, NOT OVERHEAD DOORS?
 SEE 1027.1.1.
 3)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
 4) DEPENDING ON THE TYPE OF STORAGE A
 OCCUPANCY SEPERATION WALL WILL BE RE-
 QUIRED. 1HR VS 2 HR WALL.TABLE 704.1.
 5) THE PROPOSED OFFICE EXSPANSION, IS
 STORAGE TO BE CONSIDERED ABOVE THIS NEW
 CEILING?
 6) FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 2405.2.1(3) GLAZING IN AN INDIVIDUAL FIX
 ED OR OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE IS WITH-
 IN A 24" RADIUS OF THE DOOR IN A CLOSED
 POSITION.
 7) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY/ SPRINKLERED VS
 NONSPRINKLERED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026