| 2003-10-30 00:00:00 | ****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)ADDITIONAL PERMITS REQUIRED. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN.ADDITIONS OF OVER 25% MUST COMPLY |
| | WITH FBC3401.7.2, 2003 AMENDMENT. |
| | |
| | 4.)THE FLOOR PLAN OVERALL DIMENSION |
| | HAS BEEN WRITTEN OVER AND IS NOT CLEAR |
| | AND DOES NOT APPEAR TO MATCH THE SURVEY. |
| | THE DIMENSIONS MUST ADD UP TO THE TOTAL, |
| | AND MUST BE THE SAME AS THE SITE PLAN. |
| | |
| | 5.)ENERGY CALCS, SIGNED BY BOTH THE |
| | PREPARER AND THE OWNER/AGENT, ARE |
| | REQUIRED FBC13-103.1.2. |
| | |
| | 6.)THERE ARE MANY NOTES IN INK ON THE |
| | PLAN.THE NOTES MUST BE INITIALED BY |
| | THE DESIGNER OF RECORD. |
| | |
| | 7.)NOTE THAT ON THE WALL SECTION YOU |
| | HAVE SPECIFIED R19 UNDER ATTIC, 4.2 ON |
| | THE WALL.IF A 600C ENERGY CALC IS |
| | SUMBITTED THE MINIMUM INSULATION |
| | REQUIRED WOULD BE R30 AND R5 |
| | RESPECTIVELY. |
| | |
| | 8.)CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC1804.1.7, LOWEST BUILDING |
| | FLOOR ELEVATION AT THE PERIMITER OF |
| | A MONOLITHIC FOUNDATION AT HABITABLE |
| | AREAS SHALL BE A MINIMUM OF 4" ABOVE THE |
| | FINISHED GRADE.SHOW ON WALL SECTION. |
| | |
| | 9.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 10.) TWO COPIES OF ALL DOCUMENTS MUST |
| | BE SUBMITTED.ONE WILL BE RETAINED AT |
| | THE CITY AND ONE WILL BE YOUR PERMIT |
| | SET. |
| | |
| | 11.) ADDITIONAL FEES MAY BE DUE.THESE |
| | FEES WILL BE DETERMINED AFTER AREA |
| | CALCULATIONS ARE SUBMITTED ON THE PLAN. |
| | |
| | 12.) THIS JOB IS A SUBSTANTIAL |
| | IMPROVEMENT TO A RESIDENCE LOCATED IN A |
| | FLOOD ZONE. CITY OF WEST PALM BEACH |
| | MUNICIPAL CODE REQUIRES THAT THE |
| | LOWEST FLOOR BE ELEVATED TO 6" ABOVE THE |
| | BASE FLOOD ELEVATION, 94-546.PROVIDE |
| | AN ELEVATION CERTIFICATE FOR THE |
| | EXISTING HOUSE AND SHOW COMPLIANCE ON |
| | THE PLAN. |
| | |
| | 13.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 14.)A TITLE BLOCK FOR THE ENGINEER |
| | IS REQUIRED, FAC61G15-23.001. |
| | |
| | 15.)GABLE ENDS ARE TO BE STRUCTURALLY |
| | CONTINUOUS, FBC2117.1. |
| | |
| | 16.)A STATEWIDE OR LOCAL PRODUCT |
| | APPROVAL IS REQUIRED FOR WINDOWS, DOORS, |
| | TRUSS ANCHORS AND IMPACT PROTECTION, |
| | FAC9B-72.SEE THE DCA WEBSITE, |
| | WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/ |
| | PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM |
| | FOR MORE INFORMATION. |
| | |
| | 17.)THERE IS A NOTE ON THE PLAN TO |
| | "MAKE EXIST WINDOW COMPLY W/EGRESS". |
| | SHOW HOW THIS COMPLIES WITH FBC1005.4 |
| | BY GIVING THE WINDOW SIZE AND TYPE. |
| | |
| | 18.)IMPACT PROTECTION REQUIRED FBC |
| | 1606.1.4. |
| | |
| | 19.)THERE IS A REFERENCE TO SBC (NOTE |
| | AT THE WALL SECTION); CURRENT CODE IS |
| | FBC. |
| | |
| | 20.)ATTIC ACCESS REQUIRED TO COMPLY |
| | WITH FBC2309. |
| | |
| | 21.)PROVIDE A HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE IF SHUTTERS ARE TO |
| | BE USED, SEE ATTACHED. |