| 2003-10-14 00:00:00 | ******** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE CORRELATE PLANS SUBMITTED |
| | FOR REVIEW AND PERMITTING. |
| | ONE SET FROM ARCH MENTIONS ; SERVICE TO |
| | FEED SPORTS LIGHTING? YET, E-PLANS |
| | SUBMITTED BY ENGINEER SHOWS A COMPLETELY |
| | DIFFERENT SERVICE AND MENTIONS THAT |
| | SERVICE FEDDING SPORTS LIGHTING? |
| | PLEASE EITHER CORRELATE PLANS OR IF |
| | INDEED THESE ARE TWO SEPARATE AREAS, |
| | PLEASE CLARIFY AND PERMIT SEPARATELY IF |
| | NEED BE. |
| | |
| | 2)NOTE: PLEASE SEE SERVICE ONE, PLEASE |
| | SEE MISSING GROUNDING ELECTRODE CONDUCT- |
| | -OR PER 250.24/250.66 ETC? |
| | |
| | 3)NOTE: PLEASE SHOW CIRCUITING AND |
| | CORRELATE WITH A SUBMITTED PANEL |
| | SCHEDULE. |
| | |
| | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215.3/230.42 ETC. |
| | |
| | 5)NOTE: PLEASE SEE THAT RISER MENTIONS; |
| | NEW METER AND PLANS MENTIONS EXIST TO |
| | REMAIN? |
| | |
| | 6)NOTE: PLEASE SEE SERVICE #2, SHOW ALL |
| | CONTINUOUS LOADS AT 125%. 215.3/230.42 |
| | ETC. |
| | PLEASE ALSO CLARIFY AND CORRELATE? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |