| Notes |
| Date |
Text |
| 2003-10-10 00:00:00 | PROVISO: | | | 1.REFERENCE FIRST FLOOR DUCTWORK UNDER | | | THE HOUSE SHALL NOT BE IN OR WITHIN 6" | | | OF THE EARTH AS PER 2001 FBC(M) 603.12. | | | | | | 2.RETURN AIR FROM BEDROOM AREAS SHALL | | | COMPLY WITH THE FOLLOWING: | | | REVISION TO THE 2001 FBC(M) 601.4, | | | EFFECTIVE JUNE 30,2003: | | | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM ITS SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|