| Plan Review Notes For Permit 03100434 |
| Permit Number |
03100434 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-08 00:00:00 | DENIED: | | | RESIDENTIAL: | | | 1.PER 2001 FBC(M) 403.3, VENTILATION | | | SYSTEMS, FOR OTHER THAN R-3 (ONE & TWO | | | FAMILY DWELLINGS), SHALL BE DESIGNED TO | | | SUPPLY THE MINIMUM OUTSIDE AIR IN | | | ACCORDANCE WITH TABLE 403.3.PLEASE | | | PROVIDE OUTSIDE AIR CALCULATIONS. | | | INDICATE OUTSIDE AIR DUCT SIZE, | | | MATERIAL, LAYOUT AND INTAKE ON THE PLAN. | | | | | | 2.PLAN SHEET AC.3 INDICATES DUCT TO | | | 2ND FLOOR IN RATED SHAFT. PLEASE | | | PROVIDE SHAFT DETAIL. | | | | | | RETAIL:PLANS ARE CODE COMPLIANT. | | | | | | PLEASE NOTE: | | | PLANS DO NOT INDICATE THE USE OF THE | | | RETUAIL SPACE.BECAUSE OF THE LOCATION | | | AND PROOPERTY LINES, ALLOWANCE FOR A | | | RESTAURANT MAY BE DIFFICULT SHOULD | | | CONSIDERATION NOT BE GIVEN FOR THE | | | INSTALLATION OF GREASE DUCT NOT BE MADE | | | AT THE BEGINNING OF CONSTURCTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|