| 2003-11-03 00:00:00 | *********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE PLANS REFERENCE THE | | | 99 NEC AND WE ARE NOW UNDER THE 2002 NEC | | | AS OF 7-1-03. | | | PLEASE ADJUST PLANS. | | | | | | 2)NOTE: PLEASE ALSO SEE THE REQUIREMENT | | | FOR ARC FAULT PROTECTION HAS ALSO CHANGE | | | -D PER 210.12 | | | | | | 3)NOTE: PLEASE SHOW RECEPT REQ'D PER | | | 210.62 FOR "SHOW" WINDOW RECEPTS. FIRST | | | FLR. | | | | | | 4)NOTE: PLEASE CHECK RECEPT SPACING PER | | | 210.52 | | | | | | 5)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER NEC 220. PLEASE ALSO SHOW ALL | | | CONTINUOUS LOADS AT 125%. 215.3/230.42 | | | ETC. | | | | | | 6)NOTE: PLEASE SIZE SEC'S PER 310.16 AND | | | SERVICE SIZE. THERE IS NO OCP TO LIMIT | | | SERVICE TO 600A'S. LOAD IS ALREADY | | | SHOWN AT 593A AND CONDUCTORS ARE ONLY | | | RATED FOR 610A'S AND TOTAL SERVICE | | | PROVIDE FOR BLDG ANF UNITS IS OVER 900A' | | | -S.? 230.42 ETC. | | | | | | 7)NOTE: PLEASE SIZE GEC TO FOOTER STEEL | | | PER 250.66 AND CONNECTION PER 250.50 | | | | | | 8)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | THAT WILL HAVE AN AFFECT ON ELECTRICAL | | | PLANS. PLEASE ALSO SEE 700.12E FOR | | | CIRCUITING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|