| 2004-07-13 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE HAVE PLANS SIGNED BY |
| | ENGINEER WITH FULL LEGAL SIGNATURE AS |
| | SHOWN ON ORIGINAL PLANS FILE WITH ORIG- |
| | -INAL PLANS AND PERMIT. |
| | FS 471.025 |
| | |
| | 2)NOTE: PLEASE CORRELATE RISER AND UNITS |
| | SHOWN ON PLANS ALONG WITH LOAD CALCULAT- |
| | -IONS.PLEASE ALSO CORRELATE WITH PANEL |
| | SCHEDULES. |
| | SOME UNITS DO NOT MATCH. |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS ALONG 2' OF WALL SPACE. |
| | |
| | 4)NOTE: PLEASE SEE FBC 104.6.5 FOR |
| | INCREASE OF VALUE FOR PERMIT. PLEASE SEE |
| | BUILDING PLAN REVIEW COMMENTS FOR THIS. |
| | DUE TO INCREASE OF AREA OF BLDG TO |
| | INCLUDE ALL TRADES. |
| | |
| | 5)NOTE: PLEASE SEE POSSIBLE MISPRINT IN |
| | LOAD CALCS FOR "DETAIL UNITS". SHOULD |
| | READ RETAIL UNITS. THIS IS ONLY A NOTE. |
| | |
| | 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | NOTED ON PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE SET |
| | -S FOR REVIEW AND STAMPING. |
| | PLEASE SEE ONE SET HAS SOME ITEMS |
| | REDLINED FOR AREAS OF ABOVE COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |