| Plan Review Notes For Permit 03100433 |
| Permit Number |
03100433 |
|
| Review Stop |
B |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2005-04-19 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | STRUCTURAL SUBMITTAL ON 4/14/05 FOR | | | PRE-CAST SPECIALTIES, INC. PRE-CAST | | | HOLLOWCORE SLAB SHOP DRAWINGS AND | | | CALCULATIONS. | | | | | | 1) FBC 1604.1LIVE LOADS.UNDER | | | 'LOADING DATA', THE SUBMITTED | | | CALCULATIONS STATE A LIVE LOAD OF 30 PSF | | | WAS INPUT.SHEET 1, NOTE 11 STATES THE | | | SAME.THE REQUIRED LIVE LOAD FOR | | | DWELLINGS IS 40 PSF (30 PSF IN SLEEPING | | | ROOMS ONLY).AMEND THE PLANS AND | | | CALCULATIONS TO DEMONSTRATE COMPLIANCE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|