Plan Review Notes
Plan Review Notes For Permit 03100381
Permit Number 03100381
Review Stop B
Sequence Number 6
Notes
Date Text
2004-06-15 00:00:00SITE SPECIFIC PRODUCT APPROVAL FOR
 CUSTOM FRONT DOOR IS DENIED.
  
 1) PER BUILDING OFFICIAL, SITE SPECIFIC
 PRODUCT APPROVAL REQUIRES A SIGNED,
 SEALED AND DATED LETTER FROM AN ENGINEER
 OR ARCHITECT CERTIFYING THAT THE DOOR
 WAS BUILT TO SPECIFICATIONS AND ANOTHER
 LETTER CERTIFYING THAT THE DOOR HAS BEEN
 INSTALLED PER SPECIFICATIONS.
  
 2) SEE FBC 1707.4.1 DESIGN PRESSURES FOR
 WINDOWS AND DOORS SHALL BE CALCULATED IN
 ACCORDANCE WITH COMPONENT AND CLADDING
 WINDLOADS IN 1606. SEE FBC 1707.4.3.2
 FOR CUSTOM DOORS.
  
 3)SEE FBC 1707.4.3.3 FOR DOOR COMPONENTS
 (HINGES,LOCKSETS).
  
 4) ALL DRAWINGS, CALCULATIONS, ETC. ARE
 REQUIRED TO HAVE THE APPROPRIATE TITLE
 BLOCK AND BE SIGNED, SEALED AND DATED
 PER FS 471 OR 481.
  
 5) SUBMIT THE REQUIRED DETAILS AND SPECS
 FOR FABRICATION OF THE DOOR.(FASTENERS,
 GLUE,ETC.)
  
 6) SUBMIT THE TESTING OR CALCULATIONS
 FOR THE HARDWARE (HINGES AND LOCKSET).
  
 7) INDICATE HOW IMPACT PROTECTION FOR
 GLAZING WILL BE PROVIDED. SEE FBC 1606.1
 .4
  
 ALSO SEE COMMENTS FROM PERMIT # 04010614
 0