| Plan Review Notes For Permit 03100381 |
| Permit Number |
03100381 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2004-06-15 00:00:00 | SITE SPECIFIC PRODUCT APPROVAL FOR | | | CUSTOM FRONT DOOR IS DENIED. | | | | | | 1) PER BUILDING OFFICIAL, SITE SPECIFIC | | | PRODUCT APPROVAL REQUIRES A SIGNED, | | | SEALED AND DATED LETTER FROM AN ENGINEER | | | OR ARCHITECT CERTIFYING THAT THE DOOR | | | WAS BUILT TO SPECIFICATIONS AND ANOTHER | | | LETTER CERTIFYING THAT THE DOOR HAS BEEN | | | INSTALLED PER SPECIFICATIONS. | | | | | | 2) SEE FBC 1707.4.1 DESIGN PRESSURES FOR | | | WINDOWS AND DOORS SHALL BE CALCULATED IN | | | ACCORDANCE WITH COMPONENT AND CLADDING | | | WINDLOADS IN 1606. SEE FBC 1707.4.3.2 | | | FOR CUSTOM DOORS. | | | | | | 3)SEE FBC 1707.4.3.3 FOR DOOR COMPONENTS | | | (HINGES,LOCKSETS). | | | | | | 4) ALL DRAWINGS, CALCULATIONS, ETC. ARE | | | REQUIRED TO HAVE THE APPROPRIATE TITLE | | | BLOCK AND BE SIGNED, SEALED AND DATED | | | PER FS 471 OR 481. | | | | | | 5) SUBMIT THE REQUIRED DETAILS AND SPECS | | | FOR FABRICATION OF THE DOOR.(FASTENERS, | | | GLUE,ETC.) | | | | | | 6) SUBMIT THE TESTING OR CALCULATIONS | | | FOR THE HARDWARE (HINGES AND LOCKSET). | | | | | | 7) INDICATE HOW IMPACT PROTECTION FOR | | | GLAZING WILL BE PROVIDED. SEE FBC 1606.1 | | | .4 | | | | | | ALSO SEE COMMENTS FROM PERMIT # 04010614 | | | 0 |
|