Date Text
2003-12-17 00:00:00*************** UNSAT **********
  
 1)NOTE: PLEASE SEE THAT 200A PANEL IS
 SHOWING ON PANEL SCHEDULE FEEDING 125A
 PANEL?? PLEASE SHOW OCP FOR SUB FEED
  
 2)NOTE: PLEASE SEE MISSING RECEPT IN
 DEN BATH. 210.52D/ ALSO GFI 210.8
  
 3)NOTE: PLEASE VERIFY GAS APPLIANCES
 STILL SHOWS A 220V FEED?
  
 PLEASE CALL TO GO OVER POSSIBLE PROVISO.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  