| 2003-10-20 00:00:00 | ************ UNSAT ******************** |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION OF SERVICE |
| | ON PLANS. PLANS SHOW BOTH SUB-PANELS. |
| | |
| | 2)NOTE: PLEASE SHOW/LIST PANEL SCHEDULE |
| | FOR MCB OUTSIDE. PLEASE SHOW/LIST THE |
| | OCP FOR BOTH SUB PANELS. |
| | |
| | 3)NOTE: PLEASE CLARIFY 125A SUB PANEL |
| | SHOWN ON RISER W/ 2/0'S. THIS SIZE OF |
| | CONDUCTOR IS PERMITTED HOWEVERTHIS IS |
| | ABOUT 3X WHAT IS REQD. IF SHOWN AS 2/0 |
| | THEN 2/0 WILL BE REQ'D. |
| | PLEASE ALSO SEE THAT 125A SUB PANEL IS |
| | SHOWN AS 42 CIRCUIT. PLEASE SEE THAT |
| | 125A PANELS ARE NOT MADE AS 42 CIRCUIT. |
| | PLEASE ADJUST. |
| | |
| | 4)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | FOR ALL ROOMS ON PLANS. |
| | |
| | 5)NOTE: PLEASE SEE THAT WE ARE NOW UNDER |
| | THE 2002 NEC AND PLANS REF CODES FROM |
| | 99 NEC. |
| | |
| | 6)NOTE: PLEASE SEE 210.52 FOR A COUPLE |
| | OF RECEPTS MISSING IN WHAT APPEARS TO BE |
| | BEDROOMS ON UPPER LEVEL. |
| | |
| | 7)NOTE: PLEASE SEE 210.52C1, KITCHEN |
| | COUNTERSPACE RECEPT SPACING. SEE LOCAT- |
| | -ION ON OUTSIDE WALL. HIGHLIGHTED ON |
| | ONE SET OF PLANS. |
| | |
| | 8)NOTE: PLEASE SEE 424.3B FOR SIZING |
| | OF OCP FOR A/C AHU'S. 125% MIN. |
| | |
| | 9)NOTE: PLEASE SEE OCP SHOWN FOR DRYER |
| | . MAX OCP IS TO BE 150%. MIN 125% |
| | 422.13 |
| | 10)NOTE: PLEASE VERIFY LOAD FOR ELEC |
| | OVENS AND LOADS AND OCP FOR GAS APPL |
| | SHOWN AS 2POLE/ 2200 |
| | PLEASE ALSO SEE OCP SHOWN FOR WATER |
| | HEATER AT 2P30A AND WATER HEATER IS |
| | SHOWN AS GAS. |
| | |
| | 11)NOTE: PLEASE PROVIDE ALL LICENSE #'S |
| | ON TITLE BLOCK, INCLUDING "FIRM'S #. |
| | FAC 61G1-16.004/ FS 471 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |