| Date |
Text |
| 2003-11-07 00:00:00 | UNSAT |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT TWO COPIES OF A SURVEY. |
| | INDICATE THE FLOOD ZONE. |
| | |
| | 4) PROVIDE DOCUMENTATION THAT LOT HAS |
| | BEEN SUBDIVIDED RECORDED WITH PALM BEACH |
| | COUNTY. PROVIDE PROPERTY CONTROL NUMBER |
| | FOR NEW LOT FROM PBC. |
| | |
| | 5) PLEASE REVISE THE STRUCTURAL NOTES ON |
| | A1. THE STRUCTURE IS NOT LOCATED IN A |
| | HIGH VELOCITY HURRICANE ZONE. WEST PALM |
| | BEACH IS NOT IN THE HVHZ. THE INTERNAL |
| | PRESSURE COEFFICENT FOR AN ENCLOSED |
| | STRUCTURE IS + OR - 0.18. THE BASIC |
| | PRESSURE OF 68 PSF APPEARS TO BE TOO |
| | HIGH FOR THIS STRUCTURE. PLEASE SUBMIT |
| | YOUR CALCULATIONS. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND LISTING INFORMATION FOR THE PREFAB |
| | FIREPLACE. |
| | |
| | 7) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| | OPENINGS ON THE PLAN. FBC 2309.6 |
| | |
| | 8) SPECIFY THE REQUIRED DESIGN PRESSURES |
| | FOR THE TWO GARAGE DOORS. |
| | |
| | 9) SUBMIT INFORMATION FROM THE WINDOW |
| | MANUFACTURER INDICATING THAT THE 3'8" X |
| | 5'4" CASEMENT WINDOWS COMPLY WITH THE |
| | 20" CLEAR OPENING WIDTH REQUIRED FOR |
| | EGRESS PER FBC 1005.4.4. |
| | |
| | 10) SPECIFY THE TYPE OF WELD ON THE |
| | STEEL COLUMN BASE DETAIL ON A2. |
| | |
| | 11) INDICATE HOW THE WIND PRESSURES FOR |
| | THE WINDOW AND DOOR OPENINGS WERE |
| | DETERMINED. SUBMIT CALCULATIONS. |
| | |
| | 12) ON SHEET A2 THE COLUMN PADS F3 AND |
| | F5 ARE INCORRECTLY DESIGNATED AS |
| | MONOLITHIC FOOTINGS IN THE FOOTING |
| | SCHEDULE. |
| | |
| | 13) INDICATE ON THE SECTIONS ON A9 THAT |
| | THE FINISH FLOOR ELEVATION AT HABITABLE |
| | AREAS IS REQUIRED TO BE 4" ABOVE FINAL |
| | GRADE AND THE BOTTOM OF THE FOOTER IS |
| | TO BE A MINIMUM OF 12" BELOW GRADE. |
| | SEE CITY AMENDMENTS TO FBC 1804.1.7 AND |
| | FBC 1804.1.3. |
| | |
| | 14) THE FBC MECH. CODE 303.4 REQUIRES |
| | THAT APPLIANCES ARE PROTECTED FROM |
| | DAMAGE BY APPROVED BARRIERS. SPECIFY HOW |
| | THE GAS WATER HEATER IN THE GARAGE WILL |
| | BE PROTECTED. |
| | |
| | 15) PROVIDE A SECTION/DETAIL AT THE WOOD |
| | FRAME TOWER INDICATING THE INSULATION, |
| | CEILING TYPE, ALL CONNECTORS, ETC. |
| | |
| | 16) PROVIDE DETAIL OF THE OPENING FOR |
| | THE ARCH WINDOWS AT BATH #1 ON THE |
| | SECOND FLOOR ABOVE THE ENTRY. |
| | |
| | 17)SPECIFY THE LOCATION AND THE MATERIAL |
| | FOR THE FLOOR/CEILING DRAFTSTOPPING |
| | SEPARATING IT INTO AREAS OF NO MORE THAN |
| | 500 SQFT. SEE FBC 2305.2.2. |
| | |
| | 18)1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | PLEASE REVISE THE CONNECTOR SCHEDULE ON |
| | SHEET A6 TO VALUES THAT DO NOT INCLUDE A |
| | STRESS INCREASE ON THE STEEL CONNECTIONS |
| | PROVIDE THE VALUES FOR ALL OF THE |
| | CONNECTORS SPECIFIED. |
| | |
| | 19) SPECIFY THE CONNECTORS FOR THE |
| | GIRDERS AT THE MASONRY WALLS. INDICATE |
| | LOCATIONS WHERE DETAIL 1 ON A6 ARE USED. |
| | |
| | 20) PROVIDE DETAILS FOR THE DIFFERENT |
| | CONFIGURATIONS OF STEEL COLUMN CAPS |
| | SUPPORTING THE STEEL BEAM, CONCRETE BEAM |
| | AND WOOD GIRDERS. SOME ARE CARRYING |
| | BEAMS OF DIFFERENT MATERIALS CONVERGING |
| | FROM DIFFERENT DIRECTIONS. |
| | |
| | 21) SUBMIT SHOP DRAWINGS FOR GUARDRAILS |
| | THAT INDICATE THE SPECIFIC MATERIAL, |
| | ANCHORING METHODS, FASTENERS, ETC. |
| | SPECIFY THAT INTERMEDIATE RAILS AND |
| | ORNAMENTAL PATTERN WILL REJECT A 4" |
| | SPHERE AND BOTTOM RAIL WILL REJECT A 2" |
| | SPHERE. SEE FBC 1015 |
| | |
| | 22) INDICATE THE DIMENSIONS OF THE |
| | CANTILEVER BALCONY ON THE PLAN. |
| | |
| | 23) SPECIFY THE CONNECTORS FOR THE WOOD |
| | FLOOR TRUSSES. |
| | |
| | 24) SPECIFY THE FIREBLOCKING AT THE TOP |
| | AND BOTTOM OF STAIR RUNS ON SHEET A9. |
| | SEE FBC 2305.1.4. |
| | |
| | 25) SPECIFY ON A9 THAT THE GUARDRAILS |
| | FOR THE STAIRS WILL REJECT A 4" SPHERE |
| | FROM PASSING THROUGH THE INTERMEDIATE |
| | RAILS AND THE TRIANGULAR OPENING FORMED |
| | BY THE TREAD, RISER AND BOTTOM OF THE |
| | GUARDRAIL SHALL REJECT A 6" SPHERE. |
| | SEE FBC 1015.3. SPECIFY GUARDRAIL |
| | METHOD OF ATTACHMENT. |
| | |
| | 26) CORRECT THE TYPO ON THE WALL SECTION |
| | ON A9. SHOULD BE SCREEN VENT. |
| | |
| | 27) PROVIDE BUCK DETAILS FOR THE SIDES |
| | OF THE WINDOWS, DOORS AND GARAGE DOORS. |
| | |
| | 28)SITE SPECIFIC ENGINEERING IS REQUIRED |
| | FOR THE CUSTOM FRONT DOOR. SEE THE |
| | ATTACHED FORM. |
| | |
| | 29) REVISE THE ATTIC INSULATION R VALUE |
| | ON THE WALL SECTIONS ON A9 TO AGREE WITH |
| | THE ENERGY CALCULATIONS WHICH LIST THE |
| | ATTIC INSULATION AS R-30. |
| | |
| | 30) REVISE THE CLAY MISSION ROOF TILE |
| | SPECIFIED ON THE PLAN TO CONCRETE |
| | MISSION TILE AS INDICATED BY THE PRODUCT |
| | APPROVAL SUBMITTED. |
| | |
| | 31) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - FRENCH DOORS WITH SIDELITES |
| | - GARAGE DOORS |
| | - METAL RAISED PANEL DOORS |
| | PRODUCT APPROVALS SUBMITTED AFTER |
| | OCTOBER 1, 2003 ARE REQUIRED TO COMPLY |
| | WITH THE FLORIDA PRODUCT APPROVAL SYSTEM |
| | FOR INFORMATION SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET WHICH LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE PRODUCT APPROVAL, SUBMIT AN |
| | APPLICATION FOR LOCAL PRODUCT APPROVAL |
| | PER RULE 9B-72. SEE ATTACHMENT. |
| | |
| | 32) THE WINDOWS AND DOORS ARE HAVE |
| | IMPACT RESISTANT GLAZING. THE PRODUCT |
| | APPROVALS FOR STORM PANELS ARE ONLY |
| | REQUIRED FOR GLAZING PROTECTION. |
| | |
| | 33) REFER TO NOTES ON THE PLANS AND |
| | PLEASE SUBMIT A COPY OF THE REVIEWED |
| | PLANS ALONG WITH THE REVISED PLANS. THIS |
| | WILL HELP TO EXPEDITE THE PLAN REVIEW. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |