Plan Review Notes For Permit 03100381
Permit Number 03100381
Review Stop B
Sequence Number 1
Notes
Date Text
2003-11-07 00:00:00UNSAT
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF A SURVEY.
 INDICATE THE FLOOD ZONE.
  
 4) PROVIDE DOCUMENTATION THAT LOT HAS
 BEEN SUBDIVIDED RECORDED WITH PALM BEACH
 COUNTY. PROVIDE PROPERTY CONTROL NUMBER
 FOR NEW LOT FROM PBC.
  
 5) PLEASE REVISE THE STRUCTURAL NOTES ON
 A1. THE STRUCTURE IS NOT LOCATED IN A
 HIGH VELOCITY HURRICANE ZONE. WEST PALM
 BEACH IS NOT IN THE HVHZ. THE INTERNAL
 PRESSURE COEFFICENT FOR AN ENCLOSED
 STRUCTURE IS + OR - 0.18. THE BASIC
 PRESSURE OF 68 PSF APPEARS TO BE TOO
 HIGH FOR THIS STRUCTURE. PLEASE SUBMIT
 YOUR CALCULATIONS.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE PREFAB
 FIREPLACE.
  
 7) SPECIFY THE SIZE OF THE ATTIC ACCESS
 OPENINGS ON THE PLAN. FBC 2309.6
  
 8) SPECIFY THE REQUIRED DESIGN PRESSURES
 FOR THE TWO GARAGE DOORS.
  
 9) SUBMIT INFORMATION FROM THE WINDOW
 MANUFACTURER INDICATING THAT THE 3'8" X
 5'4" CASEMENT WINDOWS COMPLY WITH THE
 20" CLEAR OPENING WIDTH REQUIRED FOR
 EGRESS PER FBC 1005.4.4.
  
 10) SPECIFY THE TYPE OF WELD ON THE
 STEEL COLUMN BASE DETAIL ON A2.
  
 11) INDICATE HOW THE WIND PRESSURES FOR
 THE WINDOW AND DOOR OPENINGS WERE
 DETERMINED. SUBMIT CALCULATIONS.
  
 12) ON SHEET A2 THE COLUMN PADS F3 AND
 F5 ARE INCORRECTLY DESIGNATED AS
 MONOLITHIC FOOTINGS IN THE FOOTING
 SCHEDULE.
  
 13) INDICATE ON THE SECTIONS ON A9 THAT
 THE FINISH FLOOR ELEVATION AT HABITABLE
 AREAS IS REQUIRED TO BE 4" ABOVE FINAL
 GRADE AND THE BOTTOM OF THE FOOTER IS
 TO BE A MINIMUM OF 12" BELOW GRADE.
 SEE CITY AMENDMENTS TO FBC 1804.1.7 AND
 FBC 1804.1.3.
  
 14) THE FBC MECH. CODE 303.4 REQUIRES
 THAT APPLIANCES ARE PROTECTED FROM
 DAMAGE BY APPROVED BARRIERS. SPECIFY HOW
 THE GAS WATER HEATER IN THE GARAGE WILL
 BE PROTECTED.
  
 15) PROVIDE A SECTION/DETAIL AT THE WOOD
 FRAME TOWER INDICATING THE INSULATION,
 CEILING TYPE, ALL CONNECTORS, ETC.
  
 16) PROVIDE DETAIL OF THE OPENING FOR
 THE ARCH WINDOWS AT BATH #1 ON THE
 SECOND FLOOR ABOVE THE ENTRY.
  
 17)SPECIFY THE LOCATION AND THE MATERIAL
 FOR THE FLOOR/CEILING DRAFTSTOPPING
 SEPARATING IT INTO AREAS OF NO MORE THAN
 500 SQFT. SEE FBC 2305.2.2.
  
 18)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 PLEASE REVISE THE CONNECTOR SCHEDULE ON
 SHEET A6 TO VALUES THAT DO NOT INCLUDE A
 STRESS INCREASE ON THE STEEL CONNECTIONS
 PROVIDE THE VALUES FOR ALL OF THE
 CONNECTORS SPECIFIED.
  
 19) SPECIFY THE CONNECTORS FOR THE
 GIRDERS AT THE MASONRY WALLS. INDICATE
 LOCATIONS WHERE DETAIL 1 ON A6 ARE USED.
  
 20) PROVIDE DETAILS FOR THE DIFFERENT
 CONFIGURATIONS OF STEEL COLUMN CAPS
 SUPPORTING THE STEEL BEAM, CONCRETE BEAM
 AND WOOD GIRDERS. SOME ARE CARRYING
 BEAMS OF DIFFERENT MATERIALS CONVERGING
 FROM DIFFERENT DIRECTIONS.
  
 21) SUBMIT SHOP DRAWINGS FOR GUARDRAILS
 THAT INDICATE THE SPECIFIC MATERIAL,
 ANCHORING METHODS, FASTENERS, ETC.
 SPECIFY THAT INTERMEDIATE RAILS AND
 ORNAMENTAL PATTERN WILL REJECT A 4"
 SPHERE AND BOTTOM RAIL WILL REJECT A 2"
 SPHERE. SEE FBC 1015
  
 22) INDICATE THE DIMENSIONS OF THE
 CANTILEVER BALCONY ON THE PLAN.
  
 23) SPECIFY THE CONNECTORS FOR THE WOOD
 FLOOR TRUSSES.
  
 24) SPECIFY THE FIREBLOCKING AT THE TOP
 AND BOTTOM OF STAIR RUNS ON SHEET A9.
 SEE FBC 2305.1.4.
  
 25) SPECIFY ON A9 THAT THE GUARDRAILS
 FOR THE STAIRS WILL REJECT A 4" SPHERE
 FROM PASSING THROUGH THE INTERMEDIATE
 RAILS AND THE TRIANGULAR OPENING FORMED
 BY THE TREAD, RISER AND BOTTOM OF THE
 GUARDRAIL SHALL REJECT A 6" SPHERE.
 SEE FBC 1015.3. SPECIFY GUARDRAIL
 METHOD OF ATTACHMENT.
  
 26) CORRECT THE TYPO ON THE WALL SECTION
 ON A9. SHOULD BE SCREEN VENT.
  
 27) PROVIDE BUCK DETAILS FOR THE SIDES
 OF THE WINDOWS, DOORS AND GARAGE DOORS.
  
 28)SITE SPECIFIC ENGINEERING IS REQUIRED
 FOR THE CUSTOM FRONT DOOR. SEE THE
 ATTACHED FORM.
  
 29) REVISE THE ATTIC INSULATION R VALUE
 ON THE WALL SECTIONS ON A9 TO AGREE WITH
 THE ENERGY CALCULATIONS WHICH LIST THE
 ATTIC INSULATION AS R-30.
  
 30) REVISE THE CLAY MISSION ROOF TILE
 SPECIFIED ON THE PLAN TO CONCRETE
 MISSION TILE AS INDICATED BY THE PRODUCT
 APPROVAL SUBMITTED.
  
 31) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRENCH DOORS WITH SIDELITES
 - GARAGE DOORS
 - METAL RAISED PANEL DOORS
 PRODUCT APPROVALS SUBMITTED AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL SYSTEM
 FOR INFORMATION SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET WHICH LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE PRODUCT APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL
 PER RULE 9B-72. SEE ATTACHMENT.
  
 32) THE WINDOWS AND DOORS ARE HAVE
 IMPACT RESISTANT GLAZING. THE PRODUCT
 APPROVALS FOR STORM PANELS ARE ONLY
 REQUIRED FOR GLAZING PROTECTION.
  
 33) REFER TO NOTES ON THE PLANS AND
 PLEASE SUBMIT A COPY OF THE REVIEWED
 PLANS ALONG WITH THE REVISED PLANS. THIS
 WILL HELP TO EXPEDITE THE PLAN REVIEW.
  