| 2003-10-30 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN; EXISTING AND NEW TOTAL.ADDITIONS |
| | OF OVER 25% MUST COMPLY WITH FBC3407.1.2 |
| | 2003 AMENDMENT.NOTE ON PLAN (GFCI, |
| | SMOKE DETECTORS). |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)ENERGY CALCS SIGNED BY BOTH THE |
| | PREPARER AND OWNER/AGENT REQUIRED |
| | FBC13-103.1.2. |
| | |
| | 4.)PE LICENSE NUMBER REQUIRED ON EACH |
| | SHEET, FAC61G15-23.002. |
| | |
| | 5.)CONFIRM THAT THE ADDITION DOES NOT |
| | BLOCK THE ONLY EGRESS THAT COMPLIES |
| | WITH FBC1005.4 FOR THE EXISTING BEDROOM. |
| | |
| | 6.)SHEET 3, MTS12, A WOOD TO WOOD |
| | CONNECTOR IS SPECIFIED IN A WOOD TO |
| | MASONRY APPLICATION.ADDRESS. |
| | |
| | 7.)TYPICAL WALL SECTION, SHEET 3, |
| | BOTTOM OF THE FOUNDATION IS REQUIRED |
| | TO BE A MINIMUM OF 12" BELOW GRADE, |
| | FBC1804.1.3. |
| | |
| | 8.)CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC1804.1.7, FLOOR ELEVATION |
| | SHALL BE A MINIMUM OF 4" ABOVE FINISHED |
| | GRADE, REVISE WALL SECTION. |
| | |
| | 9.)A ROOF TILE NOA WAS SUBMITTED, |
| | CLARIFY. |
| | |
| | 10.) EFFECTIVE OCTOBER 1, 2003, EITHER A |
| | STATEWIDE OR LOCAL PRODUCT APPROVAL IS |
| | REQUIRED.FOR MORE INFORMATION, SEE |
| | WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/ |
| | PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM |
| | |
| | PRODUCT APPROVAL WILL BE REQUIRED FOR |
| | THE SLIDING GLASS DOOR AND IMPACT |
| | PROTECTION FOR THE DOOR AS WELL AS THE |
| | MODIFIED BITUMEN AND SINGLE HUNG WINDOW. |
| | |
| | 11.) ADDITIONAL FEES DUE, $3.90, SEE |
| | ATTACHED BZ231392. |