Date Text
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT ME-1 INDICATE ON SANITARY RISER
 DIAGRAM WHERE THE EXISTING TOILET ROOMS
 THAT WILL BE DELETED WILL BE CAPPED OFF.
 ALL CAPPED OFF PLUMBING SHALL BE LEFT
 UNCOVERED UNTILL INSPECTED.
 2) SHT ME-1 SANITARY RISER DIAGRAM IN-
 DICATES THAT THE ONLY PIPING TO BE DONE
 WILL BE THE VENTING FOR THE THREE SINKS.
 IF WASTE LINES WILL BE RUN PLEASE IN-
 DICATE ON PLANS.
 3) 61G15-23.002 IF ENGINEER OF RECORD
 HAS A TITLE BLOCK THEN HE SHALL ALSO
 SIGN, SEAL, AND DATE PLANS.
  