| Plan Review Notes For Permit 03100200 |
| Permit Number |
03100200 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-20 00:00:00 | *********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | | PLACE ALL LICENSE INFORMATION ON TITLE | | | BLOCKS. FS 471 | | | PLEASE SEE THAT THIS IS REQ'D FOR ALL | | | TRADES WEATHER OR NOT THE COMMENT MAY | | | OR MAY NOT COME FROM OTHER REVIEWERS. | | | | | | 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | | PROTECTED CIRCUITS. PLEASE SEE THAT WE | | | ARE NOW UNDER 2002 NEC AND ARC FAULT | | | PROTECTTION HAS CHANGED FROM 99 NEC. | | | | | | PLEASE SUBMI THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|