2003-11-20 00:00:00PROVISO:
 DETAIL 1 ON PLAN 2 OF 3 IS NOT EXCEPTED.
 PLAN VIEW INDICATES GREASE DUCT LOUVER
 TERMINATING IN THE "ATTIC" SPACE INSTEAD
 OF AN OUTSIDE WALL PER 501.3.PLAN DOES
 NOT REFLECT THE SAME TERMIANTION POINTS
 AS DETAIL 2 ON PAGE 2, FLOOR PLAN ON
 SHEET 1 OR 3.
  
 PLEASE NOTE CLEANOUTS REQUIRED IN
 ACCORDANCE WITH 506.3.11.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.