2003-10-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
  
 1) SECTION 909.1 LAUNDRY SINK AND WASH
 MACHINE SHALL CONNECT DOWNSTREAM OF THE
 BATHROOM GROUP WET VENT.
 2) SECTION 802.4 WASH MACHINE REQUIRES
 A STANDPIPE.
 3) SECTION 708.10 CLEANOUT FOR WASH
 MACHINE SHALL BE 4' ABOVE THE FLOOR FOR
 ACCESS.
 4) SECTION 104.2.1 SANITARY RISER DIA-
 GRAM DOES NOT REFLECT THE FLOOR PLAN.
 FLOOR PLAN SHOWS A TUB AND RISER SHOWS
 A SHOWER. PLEASE CLAIRFY.
 5) SEE ATTACHED SHEET ABOUT DESIGN PRO-
 FESSIONALS. 61G1-16.004(2) LICENSE NUM-
 BER REQUIRED ON TITLE BLOCK.
  
 REVIEW BY KEN STEVENS