| Plan Review Notes For Permit 03100040 |
| Permit Number |
03100040 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-02-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. THE KITCHEN SHALL | | | CONNECT DOWNSTREAM OF THE WET-VENTEN | | | BATHROOM HORIZONTAL DRAIN. SECTION 909.1 | | | 2) ONLY ONE COPY OF NEW PLANS HAVE BEEN | | | SUBMITTED. 2 SETS OF PLANS REQUIRED FOR | | | REVIEW. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|