2004-03-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST.ITEM #4 HAS NOT
 BEEN ADDRESSED.SEE THE HIGHLIGHT ON
 THE PLAN.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 3.)SEE PREVIOUS LIST, ITEMS #1,2,5,8,
 9 STILL APPLY.
  
 4.)SUBMIT TWO SETS OF PLANS FOR
 PERMITTING.
  
 5.) THE HURRICANE SHUTTER INSTALLATION
 SCHEDULE DOESN'T SPECIFY WHICH ANCHORS
 FROM THE TEST REPORT ARE TO BE USED.
 "LEAD" IS NOT ONE OF THE CHOICES.
  
 6.)AT THE HEIGHT SPECIFIED ON THE
 SHUTTER SCHEDULE, THE ANCHORS WOULD BE
 IN HOLLOW BLOCK RATHER THAN CONCRETE.
 CHECK EDGE DISTANCE REQUIREMENTS ON THE
 TEST REPORT.
  
 7.)FLORIDA STATEWIDE, SITE SPECIFIC OR
 LOCAL PRODUCT APPROVALS REQUIRED FOR
 THE SHUTTERS.PROVIDE A SECOND COPY
 OF THE ROOF PRODUCT APPROVAL.