Plan Review Notes
Plan Review Notes For Permit 03100040
Permit Number 03100040
Review Stop M
Sequence Number 2
Notes
Date Text
2003-12-08 00:00:00DENIED - 2ND REQUEST
 RETURN AIR NOTE ON PLAN SHEET 2 IS
 INCORRECT UNLESS THE RETURN WILL BE
 DUCTED BACK TO THE AHU.RETURN TRANSFER
 DUCT SHALL BE SIZED 1 1/2 TIMES THE
 TOTAL SUPPLY TO THE MASTER BEDROOM, WITH
 A 1" (CLEAR AREA) UNDERCUT OF THE DOOR.
 TRANSFER GRILLES SHALL USE 50 SQ INCHES
 TO 100 CFM OF SUPPLY AIR. (SEE ATTACHED)
  