| 2003-12-08 00:00:00 | DENIED - 2ND REQUEST | | | RETURN AIR NOTE ON PLAN SHEET 2 IS | | | INCORRECT UNLESS THE RETURN WILL BE | | | DUCTED BACK TO THE AHU.RETURN TRANSFER | | | DUCT SHALL BE SIZED 1 1/2 TIMES THE | | | TOTAL SUPPLY TO THE MASTER BEDROOM, WITH | | | A 1" (CLEAR AREA) UNDERCUT OF THE DOOR. | | | TRANSFER GRILLES SHALL USE 50 SQ INCHES | | | TO 100 CFM OF SUPPLY AIR. (SEE ATTACHED) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|