Plan Review Notes
Plan Review Notes For Permit 03100040
Permit Number 03100040
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-22 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.
 PLANS AND TITLE BLOCK MISSING ALL INFOR-
 -MATION AS REQ'D ABOVE. PLEASE SEE THIS
 HAS BEEN THE SAME COMMENT ON MANY
 PREVIOUS REVIEWS.
 PLEASE ALSO SEE THAT WE ARE NOW RETAIN-
 -ING ONE SET OF PLANS TO BE FILED AND
 TURNED INTO THE FBPE FOR SAID VIOLATIONS
  
  
 2)NOTE: PLEASE SEE LOADS LISTED ON LOAD
 CALCUALTIONS. SHOWS DRYER AT 2500W,
 PLEASE SEE 220.18 FOR MIN LOAD.
 PLEASE SEE 220.19 FOR MIN LOAD FOR
 RANGES. PLEASE VERIFY LOAD SHOWN.
 PLEASE SEE LOAD SHOWN FOR WATER HEATER,
 PLEASE VERIFY.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS.
 PLEASE SEE NEC 220 FOR CORRECTIONS.
  
 4)NOTE: PLEASE SEE 220.12 OF THE 2002
 NEC AND LIST ON PANEL SCHEDULE.
 215.5
  
 5)NOTE: PLEASE SEE 210.52D AND 210.11C3
 LIST MIN REQ'D CIRCUIT(S) FOR BATH.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]