| 2003-10-22 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND | | | FS 471. | | | PLANS AND TITLE BLOCK MISSING ALL INFOR- | | | -MATION AS REQ'D ABOVE. PLEASE SEE THIS | | | HAS BEEN THE SAME COMMENT ON MANY | | | PREVIOUS REVIEWS. | | | PLEASE ALSO SEE THAT WE ARE NOW RETAIN- | | | -ING ONE SET OF PLANS TO BE FILED AND | | | TURNED INTO THE FBPE FOR SAID VIOLATIONS | | | | | | | | | 2)NOTE: PLEASE SEE LOADS LISTED ON LOAD | | | CALCUALTIONS. SHOWS DRYER AT 2500W, | | | PLEASE SEE 220.18 FOR MIN LOAD. | | | PLEASE SEE 220.19 FOR MIN LOAD FOR | | | RANGES. PLEASE VERIFY LOAD SHOWN. | | | PLEASE SEE LOAD SHOWN FOR WATER HEATER, | | | PLEASE VERIFY. | | | | | | 3)NOTE: PLEASE SEE LOAD CALCULATIONS. | | | PLEASE SEE NEC 220 FOR CORRECTIONS. | | | | | | 4)NOTE: PLEASE SEE 220.12 OF THE 2002 | | | NEC AND LIST ON PANEL SCHEDULE. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE 210.52D AND 210.11C3 | | | LIST MIN REQ'D CIRCUIT(S) FOR BATH. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|