| 2004-09-24 00:00:00 | REVISION CHECKLIST: |
| | 1-ARCHITECT SUBMITTING REVISION IS NOT |
| | THE SAME ARCHITECT OF RECORD.ARCHITECT |
| | NEEDS TO FOLLOW RULE 61G1-18.002 OF FL |
| | ADMINISTRATIVE CODE WHEN TAKING OVER |
| | ANOTHER ARCHITECT'S WORK. |
| | 2-ENGINEER'S REPORT: A)PROVIDE 2 COPIES |
| | WITH ORIGINAL SEAL, SIGNATURE & DATE |
| | AS REQ'D BY CHAPTER 471 FL STATUTES. |
| | B)ENGINEER TO PROVIDE ALL INFORMATION |
| | AS REQUIRED BY SEC. 1606.1.7 FBC 2001. |
| | 3-ARCHITECT AND ENGINEERTO HAVE |
| | TITLE BLOCK WITH ALL INFORMATION AS |
| | REQUIRED BY CHAPTER 481 AND 471 OF |
| | FLORIDA STATUTES. INCLUDING THE |
| | CERTIFICATE OF AUTHORIZATION. |
| | 4-PROVIDE COMPLETE INFORMATION ON WALL |
| | SECTIONS:FASTENER TYPE & SPACING |
| | FOR STUCCO METAL LATH, WALL AND ROOF |
| | SHEATHING, 2X4 REINFORCING FRAMING, |
| | FRAMING ANCHOR, ANCHOR TO TOP CHORD |
| | ETC. |
| | SEC. 104.2.1.2, TABLE 2306.1 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 5-DRAWINGS TO PROVIDE ALL INFORMATION |
| | AS REQUIRED BY SEC. 1606.1.7 FBC 2001. |
| | 6-ROOF FRAMING LAYOUT ON MAIN ROOF WAS |
| | CHANGED FROM ORIGINAL DWGS. SPECIFY |
| | ROOF TRUSS CONNECTORS FOR MODIFIED |
| | TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT |
| | 7-CLARIFY WHY IS THE TRUSS MANUFACTURER |
| | RESPONSIBLE TO VERIFY IF EXISTING |
| | TRUSSES WILL TAKE THE ADDITIONAL LOAD. |
| | THE DESIGNER IS THE ONE WHO VERIFIES |
| | THAT EXISTING STRUCTURE WILL BE ABLE |
| | TO SUPPORT THE ADDITIONAL LOAD OR |
| | REINFORCE IT AS REQUIRED. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 8-PROVIDE CERTIFICATE OF AUTHORIZATION |
| | FOR THE ENGINEERING AND ARCHITECTURAL |
| | BUSINESS AS REQUIRED BY CHAPTER 471 |
| | AND 481 FLORIDA STATUTES. |
| | |