| 2003-12-12 00:00:00 | ***************** UNSAT **************** | | | | | | PLEASE SEE THAT THERE ARE NOW SOME NEW | | | COMMENTS DUE TO RISER/PANEL SCHEDULE | | | CHANGING, ALSO SOME COMMENT FROM FIRST | | | REVIEW NEED TO BE ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE PLANS, ARCH'S LICENSE | | | # DOES NOT SEEM TOCORRELATE WITH SAID | | | SEAL. PLEASE ALSO PLEASE MAKE SURE ALL | | | SHEETS CONTAIN A CLEAR AND VISABLE | | | IMPRESSION TYPE SEAL. | | | ALL ABOVE PER FS 481.221 AND FAC 61G1-16 | | | .004. | | | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND PANELS/SCHEDULES. | | | PANELS ARE NOW SHOWN AS MCB AND RISER | | | INDICATES MLO AND DISC'S.? | | | | | | 3)NOTE: PLEASE SEE THAT AIC RATING(S) | | | ARE NOW SHOWN FOR PANELS AND BREAKERS | | | HOWEVER, NO AIC RATINGS ARE SHOWN FOR | | | MAINS. 110.9/ 215.5 | | | | | | 4)NOTE: PLEASE SEE 210.8 FOR RECEPT | | | REQ'D TO BE SHOWN AS GFI/GFI PROTECTED | | | IN GARAGE. | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210.52 BEDROOM #3./BRKFAST AREA WALL. | | | | | | 6)NOTE: PLEASE SEE FS 553.80(2)(B). | | | PLEASE SEE ATTACHED COPY AND BE SURE ALL | | | COMMENTS ARE ADDRESSED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | 561-805-6717 |
|