Plan Review Notes
Plan Review Notes For Permit 03100025
Permit Number 03100025
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-12 00:00:00***************** UNSAT ****************
  
 PLEASE SEE THAT THERE ARE NOW SOME NEW
 COMMENTS DUE TO RISER/PANEL SCHEDULE
 CHANGING, ALSO SOME COMMENT FROM FIRST
 REVIEW NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE PLANS, ARCH'S LICENSE
 # DOES NOT SEEM TOCORRELATE WITH SAID
 SEAL. PLEASE ALSO PLEASE MAKE SURE ALL
 SHEETS CONTAIN A CLEAR AND VISABLE
 IMPRESSION TYPE SEAL.
 ALL ABOVE PER FS 481.221 AND FAC 61G1-16
 .004.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS/SCHEDULES.
 PANELS ARE NOW SHOWN AS MCB AND RISER
 INDICATES MLO AND DISC'S.?
  
 3)NOTE: PLEASE SEE THAT AIC RATING(S)
 ARE NOW SHOWN FOR PANELS AND BREAKERS
 HOWEVER, NO AIC RATINGS ARE SHOWN FOR
 MAINS. 110.9/ 215.5
  
 4)NOTE: PLEASE SEE 210.8 FOR RECEPT
 REQ'D TO BE SHOWN AS GFI/GFI PROTECTED
 IN GARAGE.
  
 5)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 BEDROOM #3./BRKFAST AREA WALL.
  
 6)NOTE: PLEASE SEE FS 553.80(2)(B).
 PLEASE SEE ATTACHED COPY AND BE SURE ALL
 COMMENTS ARE ADDRESSED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW