| Date |
Text |
| 2004-01-02 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-ARCHITECT NEED CORRECT AND COMPLETE |
| | INFORMATION ON TITLE BLOCK AS REQUIRED |
| | BY CHAPTER 481 FLORIDA STATUTES WHEN |
| | SUBMITTING INFORMATION FOR PUBLIC |
| | RECORDS. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-ARCHITECT TO PROVIDE ALL INFORMATION |
| | LISTED ON SEC.1606.1.7 FBC 2001. |
| | 4-DESIGN PARAMETERS TO INCLUDE THE 30PSF |
| | OR 10PSF ATTIC LIVE LOAD AS REQ'D BY |
| | TABLE 1604.1 FBC 2001. |
| | 5-PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | COMPLETE SITE SPECIFIC ENGINEERING FOR |
| | ALL DOORS, WINDOWS, MULLIONS, ROOF |
| | TILE, TRUSS CONNECTORS, GARAGE DOORS. |
| | VISIT WWW.FLORIDABUILDING.ORG FOR |
| | INFORMATION REQUIRED TO BE SUBMITTED. |
| | **NOTE: CHECK SIZES AND TYPES OF WINDOWS |
| | DOORS SHOWN ON PLANS. PRODUCT APPROVAL |
| | NEED TO MATCH THEM. THIS INCLUDES |
| | SPECIAL WINDOW AT BREAKFAST AREA. |
| | 6-PROVIDE UL LISTING AND COMPLETE INFO. |
| | FOR FIREPLACE AND BBQ. SEC. 2806 AND |
| | 2808 FBC 2001. |
| | 7-REVISE TRUSS ANCHOR SCHEDULE TO COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001. |
| | **NOTE: SPECIFY FASTENER TYPE/NUMBER AS |
| | SHOWN ON REVISED CATALOGUE. OTHERWISE, |
| | PROVIDE ENGINEERING CALCULATIONS FOR |
| | DIFFERENT SPECIFICATIONS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 8-PROVIDE DETAIL/SPECIFICATIONS FOR |
| | CEILING INSTALLATION AT ENTRY PORCH |
| | WHEN USING STUCCO. SEE ASTM C-926 AND |
| | ASTM C-1063 FOR STUCCO THICKNESS REQ'D |
| | AND TYPE,SIZE AND SPACING OF FASTENER |
| | REQUIRED. (INFO.SUBMITTED ON SHEET A-6 |
| | ANDA-7 IS INCORRECT & NOT COMPLETE) |
| | 9-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENERS AS REQUIRED BY SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | 10-DRAWINGS NEED TO BE STAMPED BY THE |
| | COUNTY FOR IMPACT FEES. |
| | 11-PLEASE CLOUD ALL CORRECTIONS/REVISION |
| | DONE TO NEW DRAWINGS TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | 12-SHEET A-7:A)CLARIFY WHERE ARE DETAILS |
| | P AND L SHOWN ON ROOF FRAMING PLAN?. |
| | B)MISSING SOME CONNECTION DETAILS. EG: |
| | CONNECTIONS FOR COLS AT ENTRY PORCH. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | C)ROOF FRAMING PLAN IS MISSING CHIMNEY |
| | LOCATION AND FRAMING AROUND IT. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ @ 805-6712. |