Plan Review Notes
Plan Review Notes For Permit 03100025
Permit Number 03100025
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-02 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT NEED CORRECT AND COMPLETE
 INFORMATION ON TITLE BLOCK AS REQUIRED
 BY CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING INFORMATION FOR PUBLIC
 RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 LISTED ON SEC.1606.1.7 FBC 2001.
 4-DESIGN PARAMETERS TO INCLUDE THE 30PSF
 OR 10PSF ATTIC LIVE LOAD AS REQ'D BY
 TABLE 1604.1 FBC 2001.
 5-PROVIDE FLORIDA PRODUCT APPROVAL OR
 COMPLETE SITE SPECIFIC ENGINEERING FOR
 ALL DOORS, WINDOWS, MULLIONS, ROOF
 TILE, TRUSS CONNECTORS, GARAGE DOORS.
 VISIT WWW.FLORIDABUILDING.ORG FOR
 INFORMATION REQUIRED TO BE SUBMITTED.
 **NOTE: CHECK SIZES AND TYPES OF WINDOWS
 DOORS SHOWN ON PLANS. PRODUCT APPROVAL
 NEED TO MATCH THEM. THIS INCLUDES
 SPECIAL WINDOW AT BREAKFAST AREA.
 6-PROVIDE UL LISTING AND COMPLETE INFO.
 FOR FIREPLACE AND BBQ. SEC. 2806 AND
 2808 FBC 2001.
 7-REVISE TRUSS ANCHOR SCHEDULE TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001.
 **NOTE: SPECIFY FASTENER TYPE/NUMBER AS
 SHOWN ON REVISED CATALOGUE. OTHERWISE,
 PROVIDE ENGINEERING CALCULATIONS FOR
 DIFFERENT SPECIFICATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING INSTALLATION AT ENTRY PORCH
 WHEN USING STUCCO. SEE ASTM C-926 AND
 ASTM C-1063 FOR STUCCO THICKNESS REQ'D
 AND TYPE,SIZE AND SPACING OF FASTENER
 REQUIRED. (INFO.SUBMITTED ON SHEET A-6
 ANDA-7 IS INCORRECT & NOT COMPLETE)
 9-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 10-DRAWINGS NEED TO BE STAMPED BY THE
 COUNTY FOR IMPACT FEES.
 11-PLEASE CLOUD ALL CORRECTIONS/REVISION
 DONE TO NEW DRAWINGS TO EXPEDITE THE
 REVIEW PROCESS.
 12-SHEET A-7:A)CLARIFY WHERE ARE DETAILS
 P AND L SHOWN ON ROOF FRAMING PLAN?.
 B)MISSING SOME CONNECTION DETAILS. EG:
 CONNECTIONS FOR COLS AT ENTRY PORCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 C)ROOF FRAMING PLAN IS MISSING CHIMNEY
 LOCATION AND FRAMING AROUND IT. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ @ 805-6712.