| Date |
Text |
| 2003-10-22 00:00:00 | *************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G1-16.004 , |
| | PLEASE SEE THAT ALL LICENSE INFORMATION |
| | IS REQ'D TO BE ON TITLE BLOCK. PLEASE |
| | INCLUDE FIRM'S # ALONG WITH ARCH'S#. |
| | PLEASE SEE THAT RAISED SEALED MUST BE |
| | CLEARLY VISABLE AND FULLY READABLE. |
| | |
| | 2)NOTE: PLEASE SIZE SEC'S FOR A 400A |
| | SERVICE PER 310.15(B)(6) 400MCM MIN. |
| | |
| | 3)NOTE: PLEASE INCLUDE BLDG FOOTER |
| | STEEL AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM AS REQ'D IN 250.50 |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL SERVICE EQUIPMENT. MAINS, PANELS AND |
| | BREAKERS ARE ALL REQ'D TO BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT. 110.9 |
| | |
| | 5)NOTE: PLEASE SEE PLAN, SHOWS ONLY ONE |
| | DISC AT SERVICE LOCATION. |
| | |
| | 6)NOTE: PLEASE LIST ALL THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PLEASE SEE THAT WE ARE NOW |
| | UNDER THE 2002 NEC AND ARC FAULT PROTECT |
| | -ION IS NO LONGER JUST RTECEPTS. |
| | |
| | 7)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | FOR ALL ROOMS. |
| | |
| | 8)NOTE: PLEASE MOVE SD IN MASTER BEDRM? |
| | INTO SLEEPING AREA. NFPA-72 8-4 |
| | |
| | 9)NOTE: PLEASE SEE THAT RECEPTS ARE TO |
| | BE W/IN 3' OF LAV/SINKS. (MAST)? |
| | 210.52D |
| | |
| | 10)NOTE: SD'S ARE REQ'D INSIDE AND OUT- |
| | -SIDE ALL SLEEPING ROOMS AND ALSO |
| | ADAPTABLE SLEEPING RMS. THESE RMS THAT |
| | MAY CONTAIN A CLOSET OR BATH RM. |
| | NFPA-72 |
| | |
| | 11)NOTE: PLEASE SEE MISSING RECEPT IN- |
| | FRONT OF DWELLING UNIT. 210.52E |
| | |
| | 12)NOTE: PLEASE SHOW RECEPT REQ'D FOR |
| | GARAGE (210.52G) AS GFI. 210.8 |
| | |
| | 13)NOTE: PLEASE SHOW MISSING REQ'D LT |
| | AND RECEPT FOR ATTIC. 210.70 AND 210.63 |
| | |
| | 14)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS. |
| | |
| | 15)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. 210.8(A)(6) |
| | |
| | 16)NOTE: PLEASE CLARIFY CIRCUIT #11? |
| | SHOWN AS 15A/ #14? |
| | |
| | 17)NOTE: PLEASE SEE THAT AN ADDITIONAL |
| | RECEPT IS REQ'D AT THE END OF PENINSULAR |
| | PLEASE SEE 210.52C 1-5 |
| | |
| | PLEASE SEE THAT ONE SET OF PLANS HAVE |
| | MOST OF THE ABOVE ITEMS HIGHLIGHTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |