Plan Review Notes
Plan Review Notes For Permit 03100025
Permit Number 03100025
Review Stop B
Sequence Number 1
Notes
Date Text
2003-11-17 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO PROVIDE ALL INFORMATION
 REQ'D BY CHAPTER 481 FLORIDA STATUTES.
 INCLUDING NAME OF PERSON SIGNING THE
 PLANS. SEE 61G1-16.004 F.A.C.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 LISTED ON SEC. 1606.1.7 FBC 2001.
 4-DESIGN PARAMETERS INFORMATION TO
 INCLUDE THE ATTIC LIVE LOAD (10PSF OR
 30PSF) AS REQUIRED BY TABLE 1604.1 FBC
 5-SPECIFY JOINTS IN CONCRETE SLAB AND/OR
 SPECIFY WWM SUPPORTS AND SPACING IN
 CONCRETE SLAB. SEE SEC. 1909.3 FBC2001
 6-AS OF OCT. 1ST 2003 CONTRACTOR NEEDS
 TO PROVIDE FLORIDA PRODUCT APPROVAL OR
 LOCAL PRODUCT APPROVAL. SEE QUESTIONS
 & ANSWERS FOR PRODUCT APPROVAL LAW ON
 WWW.FLORIDABUILDING.ORG FOR PROPER
 INFORMATION TO BE SUBMITTED.
 **NOTE:SEE COMMENTS ON PRODUCT APPROVALS
 SUBMITTED. PROVIDE PRODUCT APPROVAL
 FOR ACTUAL TYPE OF WINDOWS/DOORS TO BE
 INSTALLED.
 **PRODUCT APPROVAL REQ'D FOR: ROOF TILE,
 SINGLE HUNG WINDOWS, FIXED AND ARCHED
 WINDOWS (CHECK SIZES ON PLANS), FRENCH
 DOORS WITH SIDELITES (SEE PLANS),
 ENTRY DOORS, GARAGE DOORS, MULLIONS.
 7-CLARIFY IF USING IMPACT WINDOWS AND
 DOORS OR PROVIDE COMPLETE INFORMATION
 FOR STORM SHUTTERS.
 8-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR FIREPLACE AND BBQ. AS REQUIRED BY
 SEC. 2806 AND 2808 FBC 2001.
 9-PROVIDE COMPLETE DETAIL/SECTION AT
 INSTALLATION OF FIXED WINDOWS TO
 MULLIONS AT BREAKFAST WINDOW. SPECIFY
 ALL MATERIALS AND FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-REVISE/TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STEEL STRESS INCREASE TO BE USED.
 **NOTE: SEE USP 2003 CATALOGUE, WHICH
 IS ALREADY REVISED.PROVIDE ENGINEERING
 CALCS FOR CONNECTORS W/ FASTENER TYPE,
 NUMBER AND VALUES OTHER THAN THOSE
 PUBLISED ON THE CATALOGUE. ALSO, CHECK
 CATALOGUE FOR CORRECT DESCRIPTION OF
 CONNECTORS.
 11-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ENTRY DOORS WHEN REQUIRED BUCK NEEDS
 TO BE 2X AS REQUIRED BY THE PRODUCT
 APPROVAL. SAME FOR ARCHED WINDOWS. SEE
 CORRESPONDING PRODUCT APPROVALS.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 12-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING INSTALLATION AT ENTRY & REAR
 PORCH. SPECIFY MATERIALS/FASTENER SIZE
 SEE ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 13-SPECIFY ROOF TILE FASTENERS. SEE SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 14-LIBRARY ROOM MAY BE USED FOR SLEEPING
 PURPOSES. PROVIDE EGRESS FROM THIS RM
 OR ARCHITECT TO CLEARLY WRITE NOTE ON
 THIS ROOM THAT "THIS ROOM IS NOT TO BE
 USED FOR SLEEPING PURPOSES" AS REQ'D
 BY THE BUILDING OFFICIAL AND SECTION
 1005.4 FBC 2001.
 15-SHEET A-1: REVISE/UPDATE ALL NOTES
 AS REQUIRED. SEE COMMENTS ON PLANS AND
 RETURN REVIEWED SET TO EXPEDITE THE
 REVIEW PROCESS.
 16-SHEET A-2: A)SPECIFY COLUMN C-4 SHOWN
 ON FOUNDATION PLAN.
 B)UPDATE NOTES. SEE COMMENTS ON PLANS.
 17-SHEET A-3: SPECIFY SAFETY GLASS WHERE
 REQ'D. SEC. 2405.2 FBC 2001.
 18-SHEET A-7:CONNECTOR J IS FOR WOOD
 TO WOOD CONNECTION, BUT IS SPECIFIED
 FOR MASONRY INSTALLATION. CLARIFY. SEE
 COMMENTS ON ROOF FRAMING PLAN.
 19-SHEET A-8: A)UPDATE NOTES.
 B)CHIMNEY DETAIL. STUCCO TO BE 7/8" MIN.
 AS REQ'D BY ASTM C-926.
 C)CONNECTION DETAIL E IS INCOMPLETE.
 DOESN'T SPECIFY ANCHORS AND SIZES.
 ALSO, IS NOT CLEAR WHICH ONE TO BE
 USED ON ROOF FRAMING PLAN ACCORDING TO
 SPECIFIC LOCATION. CLARIFY AS REQ'D.
 D)CLARIFY ONE STORY WALL SECTION. FOOT'G
 SIZE. NEED 4"MIN. ABOVE GRADE AND 12"
 MIN. BELOW GRADE.
 **SPECIFY FIREBLOCKING. SEC. 2305 FBC.
 **VENTILATION IS FOR ENTIRE ROOF. NOT
 JUST FOR LIVING AREA. SEC 2309.7 FBC
 E)SEE COMMENTS ON SHEET A-7 AND RETURN
 REVIEWED SET TO EXPEDITE REVIEW.
  
 NOTE:
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.