| Plan Review Notes For Permit 03100007 |
| Permit Number |
03100007 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-08 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | | | | PLEASE LABEL THE DEVICES AND EQUIPMENT | | | WITH BRANCH CIRCUIT NUMBERS | | | CORRESPONDING TO THE PANEL SCHEDULE. | | | | | | RESUBMIT THE CORRECTED PLANS FOR REVIEW | | | PRIOR TO CALLING ROUGH ELECTRICAL | | | INSPECTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|