| 2003-10-20 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS REFERENCE 1999 |
| | NEC, AS OF 7/1/2003 WE ARE NOW UNDER |
| | THE 2002 NEC. |
| | |
| | 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12. |
| | PLEASE SEE THAT IS IT NO LONGER JUST |
| | RECEPTS. |
| | |
| | 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM |
| | COMPLETE WITH CONDUCTORS/CONDUITS AND |
| | LOAD CALCULATIONS FOR MIN REQ'D PER |
| | NEC 220. 215.5MIN LOADS PER NEC 220 |
| | |
| | 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM PER 250.50. |
| | |
| | 5)NOTE: PLEASE CLARIFY REQ'D SD'S PER |
| | NFPA-72 2-5. PLEASE SEE THAT PLANS SHOW |
| | WHAT APPEAR TO BE TELEPHONE OUTLETS |
| | AT LOCATIONS FOR SD'S? |
| | |
| | 6)NOTE: PLEASE SHOW A/C UNITS AND RECEPT |
| | -S PER 210.63. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | 2' OF WALL SPACE PER 210.52. BR#3 |
| | |
| | 8)NOTE: PLEASE SEE FS 471.025 AND FAC |
| | 61G15-23.002. PLANS ARE REQ'D TO BE |
| | ORIGINAL SIGNATURE,DATED AND SEALED BY |
| | ENGINEER OF RECORD. THIS COMMENT IS |
| | FOR ALL PAGES INCLUSIVE OF OTHER TRADES |
| | ALSO,WEATHER OR NOT IT IS ANOTHER REVIEW |
| | -ERS COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |