| 2003-10-29 00:00:00 | BUILDING CHECKLIST: |
| | 1-PLANS DON'T MATCH. PLANS SUBMITTED ARE |
| | FOR 2 DIFFERENT MODELS. |
| | 2-NEED LETTER CERTIFICATE FROM THE THIRD |
| | PARTY AGENCY AS REQ'D BY SEC. 428.4.2 |
| | FBC 2001. |
| | 3-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING BACK STAMPED DRAWINGS & RECEIPT. |
| | 4-SURVEY NEEDS ORIGINAL SIGNATURE, DATE |
| | AS REQ'D BY CHAPTER 471 FL STATUTES. |
| | 5-ENERGY CALCULATIONS: A)COMPLETE ALL |
| | INFO. ON TOP OF FORM. |
| | B)CLARIFY WHY THERE IS NOT INSULATION ON |
| | THE RAISED FLOOR . SECTION 605 CHAPTER |
| | 13 FBC 2001. |
| | C)REVISE/CLARIFY VALUE GIVEN FOR UNDER |
| | ATTIC INSULATION. SEE PLANS FOR RVALUE |
| | USED. |
| | D)PREPARER TO SIGN AND DATE BOTTOM OF |
| | FORM. SEC. 103.1.1 CHAPTER 13 FBC. |
| | E)OWNER/AGENT TO SIGN AND DATE BOTTOM OF |
| | FORM. SEC. 103.1.2 CHAPTER 13 FBC 2001 |
| | |
| | 6-LOCAL ENGINEER TO PROVIDE ALL INFO. AS |
| | LISTED ON SEC. 1606.1.7 FBC 2001. |
| | 7-LOCAL ENGINEER TO PROVIDE ALL HIS INFO |
| | AS REQ'D BY CHAPTER 471 FL. STATUTES. |
| | 8-STORM SHUTTERS: A)PROVIDE LEGIBLE AND |
| | COMPLETE DRAWINGS. PAGE ONE AND TWO. |
| | B)PROVIDE KEY PLAN AND COMPLETE INSTALLA |
| | TION SCHEDULE. |
| | C)CLEARLY MARK ON STORM SHUTTER DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| | TYPE AND SPACING TO BE USED ACCORDING |
| | TO THE DESIGN PRESSURES, PANEL SPAN, |
| | EDGE DISTANCE, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 9-SOIL TEST REPORT TO HAVE ORIGINAL |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES. |
| | 10-CONTRACTOR'S SCREEN CALLS FOR EXPIRED |
| | INSURANCE. PLEASE, UPDATE CONTRACTOR'S |
| | INFORMATION WITH PERMIT CLERK. |
| | 11-OWES $171.51 FOR UPDATED VALUE AND |
| | RADON FEES. PLEASE PAY ATTACHED |
| | RECEIPT. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |