Plan Review Notes
Plan Review Notes For Permit 03092021
Permit Number 03092021
Review Stop B
Sequence Number 8
Notes
Date Text
2005-03-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.) THE CERTIFICATE OF AUTHORIZATION
 NUMBER IS TO BE ON ENGINEERING
 DOCUMENTS, FAC61G15-23.002.
  
 2.)THE ENGINEERING FOR THE DOOR
 INCLUDES THE DOOR ITSELF, BUT NOT THE
 OTHER COMPONENTS (FRAME, HARDWARE).
 PROVIDE TEST REPORTS FOR THE OTHER
 COMPONENTS OF THE DOOR ASSEMBLY.IF THE
 TEST REPORTS DO NOT GIVE GUIDELINES FOR
 THE DOOR ASSEMBLY (PLACEMENT AND NUMBER
 OF HINGES, HOW THE HINGES WILL BE
 ATTACHED, ETC.) PROVIDE AN ENGINEERED
 SPECIFICATION.