| 2004-09-21 00:00:00 | DENIED: | | | PLAN SHEET M.2 INDICATES "FREE RETURN | | | CLOSET".THIS WILL BE CONSIDERED A | | | PLENUM AND SHALL BE CONSTRUCTED IN | | | ACCORDANCE WITH 2001 FBC CHAPTER 13 | | | SUB-SECTION 610.1.ABC.3.7, MECHANICAL | | | CLOSETS.PLEASE NOTE, PLAN SHEET A.3, | | | INDICATES THE AREA FOR A "FREE RETURN" | | | HAVING "NEW BUILT-IN CABINETS",RETURN | | | AIR PLENUMS CANNOT BE USED AS STORAGE | | | AREAS.PLEASE CLARIFY. | | | | | | PLAN SHEET M.2 HAS THE EXHAUST DUCT & | | | IN-LINE FANS IN THE RETURN PLENUM.THIS | | | IS NOT PERMITTED AS PER 2001 FBC(M) | | | 601.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|