 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE "PVC BOX" ON THE RISER MUST
 COMPLY WITH ARTICLE 314.28(A), PLEASE
 SIZE ACCORDINGLY.
  
 2} EQUIPMENT GROUNDING CONDUCTORS MUST
 BE RAN WITH APPROPRIATE FEEDERS. SEE
 REVIEWED RISER.
  
 3} PLEASE NOTE 3/0 FEEDERS SHOWN FROM
 THE 200 AMP DISCONNECT TO THE 100 AMP
 SUB PANEL ON RISER, BUT #3 FEEDERS SHOWN
 ON THE PANEL SCHEDULE. PLEASE
 CORRELATE.
  
 4} PLEASE SEE CIRCUIT #32 IN THE 200 AMP
 PANEL IS A BATH CIRCUIT, BUT SHOWN AS
 "EXERCISE" ON THE SCEDULE . PLEASE CHECK
 ALL CIRCUIT NUMBERS ON THE SCHEDULE WITH
 NUMBERS ON PLAN.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} THE GARAGE RECEPTACLE(S) MUST COMPLY
 WITH 210.8(A)(2) FOR GFCI PROTECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  