| Plan Review Notes For Permit 03092021 |
| Permit Number |
03092021 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-01-20 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE "PVC BOX" ON THE RISER MUST | | | COMPLY WITH ARTICLE 314.28(A), PLEASE | | | SIZE ACCORDINGLY. | | | | | | 2} EQUIPMENT GROUNDING CONDUCTORS MUST | | | BE RAN WITH APPROPRIATE FEEDERS. SEE | | | REVIEWED RISER. | | | | | | 3} PLEASE NOTE 3/0 FEEDERS SHOWN FROM | | | THE 200 AMP DISCONNECT TO THE 100 AMP | | | SUB PANEL ON RISER, BUT #3 FEEDERS SHOWN | | | ON THE PANEL SCHEDULE. PLEASE | | | CORRELATE. | | | | | | 4} PLEASE SEE CIRCUIT #32 IN THE 200 AMP | | | PANEL IS A BATH CIRCUIT, BUT SHOWN AS | | | "EXERCISE" ON THE SCEDULE . PLEASE CHECK | | | ALL CIRCUIT NUMBERS ON THE SCHEDULE WITH | | | NUMBERS ON PLAN. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 6} THE GARAGE RECEPTACLE(S) MUST COMPLY | | | WITH 210.8(A)(2) FOR GFCI PROTECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|