| Plan Review Notes For Permit 03092021 |
| Permit Number |
03092021 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2004-12-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE NOA SUBMITTED FOR THE DOUBLE | | | OUTSWING DOOR WITH SIDELITES | | | (01-0314.28) DOES NOT COMPLY WITH THE | | | DESIGN PRESSURES DETERMINED BY THE | | | ENGINEER (NOA HAS A LIMITATION OF | | | +-55). | | | ALSO IS NOT APPROVED FOR USE WHERE | | | WATER | | | INFILTRATION REQUIREMENT IS NEEDED. | | | THE | | | SIDELITES REQUIRE IMPACT PROTECTION.A | | | NOTE AT THE TOP OF THE NOA STATES | | | "GARAGE 3'0" ENTRY".IF THIS NOA IS | | | FOR | | | THE DOOR FROM THE INSIDE OF THE GARAGE | | | TO THE HALLWAY, A TEST REPORT IS NOT | | | REQUIRED AS IT IS CONSIDERED AN | | | INTERIOR | | | DOOR. | | | |
|