2004-07-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE USE SOME RECOGNIZED
 IDENTIFICATION METHOD TO INDICATE
 CHANGES ON THE PLAN. THE REVISION BLOCK
 INDICATES A TRIANGLE BUT NOTHING ON THE
 PLAN.
  
 INDICATE THE SIZE OF THE
 CONDUIT,GUTTERS,RACEWAYS AND ALL FEEDER
 CONDUTOR SIZES INSTALLED IN SAME. ALSO
 SHOW THE LOCATION OF ALL THE SERVICE
 EQUIPMENT SHOWN ON THE RISER DIAGRAM,
 ON THE PLAN IN THE INTENDED LOCATION.
  
 INDICATE THE INTENDED USE OF THE 15 KW
 TRANSFORMER SHOWN ON THE RISER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  