| 2004-07-29 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)IN THE FUTURE, PLEASE CLOUD ALL |
| | CHANGES.FOR THIS REVISION, HOWEVER, |
| | FOR THE A&S SHEETS PLEASE DO NOT CHANGE |
| | OUT UNLESS AFFECTED BY THIS CORRECTION |
| | LIST AS THESE SHEETS HAVE ALREADY |
| | BEEN REVIEWED AND STAMPED. |
| | |
| | 2.)SUBMIT PRODUCT APPROVALS FOR THE |
| | CUSTOM DOOR. |
| | |
| | 3.)1-A5, FIREBLOCKING REQUIRED FBC |
| | 705.3.1.1. |
| | |
| | 4.)A7 SPECIFIES TO ATTACH THE LUCITE |
| | RODS "AS REQUIRED".THE LUCITE RODS |
| | SERVE AS A GUARDRAIL AND ARE TO COMPLY |
| | WITH FBC1606.2.2, FBC1015.SHOW |
| | DIMENSIONS, DESIGN CRITERIA(FBC1606.2.2) |
| | AND ATTACHMENT COMPLYING WITH THIS |
| | DESIGN CRITERIA.DO NOT JUST GIVE |
| | CODE SECTIONS PLEASE. |
| | |
| | 5.)SPECIFY ATTACHMENT FOR THE BRACKETS |
| | FOR THE HANDRAIL, TO COMPLY WITH |
| | FBC1606.2.1, 5-A7. |
| | |
| | 6.)PROVIDE TWO COPIES OF PRODUCT |
| | APPROVALS FOR THE AWNING AND FIXED |
| | WINDOWS.IF THEY ARE NOT IMPACT, |
| | PROVIDE TWO COPIES OF THE SHUTTER |
| | PRODUCT APPROVALS. |
| | |
| | 7.)TO EXPEDITE PLAN REVIEW, PLEASE |
| | PROVIDE DESIGN PRESSURES ON THE |
| | WINDOW AND DOOR SCHEDULES.IT APPEARS |
| | THAT SOME OF THE PRODUCTS ARE NON |
| | COMPLIANT FROM THE TABLE ON S5.WHAT |
| | ARE THE NUMBERS +45/-62 (DESIGN WIND |
| | PRESSURE) FOR; THIS IS WHERE THE |
| | COMPONENTS & CLADDING PRESSURES NORMALLY |
| | ARE STATED PER FBC1606.1.7.SINCE IT |
| | UNCLEAR WHAT THE DESIGN PRESSURES ARE, |
| | PLEASE INCLUDE ON A TABLE AND SUBMIT |
| | PRODUCT APPROVALS WHICH ARE COMPLIANT. |
| | |
| | 8.)THE STRUCTURAL DETAILS SUBMITTED |
| | WITH THIS REVISION HAVE BEEN REVIEWED |
| | AND A COPY RETAINED.DO NOT RESUBMIT |
| | WITH THE PLANS; THIS IS YOUR APPROVED |
| | JOB COPY. |
| | |
| | WHEN RESUBMITTING, PLEASE REPLACE ONLY |
| | SHEETS WHICH HAVE CHANGED.SUBMIT OLD |
| | SHEETS SEPARATELY. |