Plan Review Notes
Plan Review Notes For Permit 03092021
Permit Number 03092021
Review Stop B
Sequence Number 3
Notes
Date Text
2004-07-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IN THE FUTURE, PLEASE CLOUD ALL
 CHANGES.FOR THIS REVISION, HOWEVER,
 FOR THE A&S SHEETS PLEASE DO NOT CHANGE
 OUT UNLESS AFFECTED BY THIS CORRECTION
 LIST AS THESE SHEETS HAVE ALREADY
 BEEN REVIEWED AND STAMPED.
  
 2.)SUBMIT PRODUCT APPROVALS FOR THE
 CUSTOM DOOR.
  
 3.)1-A5, FIREBLOCKING REQUIRED FBC
 705.3.1.1.
  
 4.)A7 SPECIFIES TO ATTACH THE LUCITE
 RODS "AS REQUIRED".THE LUCITE RODS
 SERVE AS A GUARDRAIL AND ARE TO COMPLY
 WITH FBC1606.2.2, FBC1015.SHOW
 DIMENSIONS, DESIGN CRITERIA(FBC1606.2.2)
 AND ATTACHMENT COMPLYING WITH THIS
 DESIGN CRITERIA.DO NOT JUST GIVE
 CODE SECTIONS PLEASE.
  
 5.)SPECIFY ATTACHMENT FOR THE BRACKETS
 FOR THE HANDRAIL, TO COMPLY WITH
 FBC1606.2.1, 5-A7.
  
 6.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR THE AWNING AND FIXED
 WINDOWS.IF THEY ARE NOT IMPACT,
 PROVIDE TWO COPIES OF THE SHUTTER
 PRODUCT APPROVALS.
  
 7.)TO EXPEDITE PLAN REVIEW, PLEASE
 PROVIDE DESIGN PRESSURES ON THE
 WINDOW AND DOOR SCHEDULES.IT APPEARS
 THAT SOME OF THE PRODUCTS ARE NON
 COMPLIANT FROM THE TABLE ON S5.WHAT
 ARE THE NUMBERS +45/-62 (DESIGN WIND
 PRESSURE) FOR; THIS IS WHERE THE
 COMPONENTS & CLADDING PRESSURES NORMALLY
 ARE STATED PER FBC1606.1.7.SINCE IT
 UNCLEAR WHAT THE DESIGN PRESSURES ARE,
 PLEASE INCLUDE ON A TABLE AND SUBMIT
 PRODUCT APPROVALS WHICH ARE COMPLIANT.
  
 8.)THE STRUCTURAL DETAILS SUBMITTED
 WITH THIS REVISION HAVE BEEN REVIEWED
 AND A COPY RETAINED.DO NOT RESUBMIT
 WITH THE PLANS; THIS IS YOUR APPROVED
 JOB COPY.
  
 WHEN RESUBMITTING, PLEASE REPLACE ONLY
 SHEETS WHICH HAVE CHANGED.SUBMIT OLD
 SHEETS SEPARATELY.