Plan Review Notes For Permit 03092021
Permit Number 03092021
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-05 00:00:00 
 PROVISO
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE THE PLANS TO ADDRESS THE
 FOLLOWING COMMENTS AND RESUBMIT FOR
 REVIEW PRIOR TO CALLING ELECTRICAL
 INSPECTIONS.
  
 1} THE FEEDER FROM THE DISCONNECT TO
 THEPANEL IS SHOWN AS CARRYING THE HIGH
 LEG TO THE GUTTER,PLEASE VERIFY.IT
 APPEARS
 TO TERMINATE THERE.
  
 2} THERE MUST BE AN EQUIPMENT GROUND
 RANTO THE PANEL FROM THE DISCONNECT PER
 250.122.
  
 3} PLEASE SHOW HOW THE 60 AMP
 DISCONNECT AT THE GUTTER IS BEING FED.IT
 IS NOT LISTED IN THE THE PANEL SCHEDULE
 FROM THE 200 AMP IF IT IS TAPPED IN THE
 GUTTER PLEASE SHOW TAP CONDUCTOR SIZE.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} THE RANGE IN THE LOAD CALC SHOULD BE
 LISTED AT 8000 VA TO COMPLY WITH 220.19.
  
 7} SMOKE DETECTOR MUST BE INSTALLED IN
 THE UPPER LEVEL PER 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718