| 2003-12-05 00:00:00 | |
| | PROVISO |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE REVISE THE PLANS TO ADDRESS THE |
| | FOLLOWING COMMENTS AND RESUBMIT FOR |
| | REVIEW PRIOR TO CALLING ELECTRICAL |
| | INSPECTIONS. |
| | |
| | 1} THE FEEDER FROM THE DISCONNECT TO |
| | THEPANEL IS SHOWN AS CARRYING THE HIGH |
| | LEG TO THE GUTTER,PLEASE VERIFY.IT |
| | APPEARS |
| | TO TERMINATE THERE. |
| | |
| | 2} THERE MUST BE AN EQUIPMENT GROUND |
| | RANTO THE PANEL FROM THE DISCONNECT PER |
| | 250.122. |
| | |
| | 3} PLEASE SHOW HOW THE 60 AMP |
| | DISCONNECT AT THE GUTTER IS BEING FED.IT |
| | IS NOT LISTED IN THE THE PANEL SCHEDULE |
| | FROM THE 200 AMP IF IT IS TAPPED IN THE |
| | GUTTER PLEASE SHOW TAP CONDUCTOR SIZE. |
| | |
| | 4} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 5} PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 6} THE RANGE IN THE LOAD CALC SHOULD BE |
| | LISTED AT 8000 VA TO COMPLY WITH 220.19. |
| | |
| | 7} SMOKE DETECTOR MUST BE INSTALLED IN |
| | THE UPPER LEVEL PER 905.2.2 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |