| Plan Review Notes For Permit 03092021 |
| Permit Number |
03092021 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | PROVISO: | | | PLEASE NOTE, REVISION TO THE 2001 | | | FBC(M) 601.4, EFFECTIVE JUNE 30,2003: | | | | | | BALANCED AIR RETURN - RETURN AIR SHALL | | | BE 1 1/2 TIMES THE CROSS SECTIONAL AREA | | | (SQ INCHES) OF THE SUPPLY DUCT ENTERING | | | THE ROOM ITS SERVING & THE DOOR HAVING | | | UNRESTRICTED 1" UNDERCUT. ALL SUPPLY AIR | | | INTO THE MASTER SUITE SHALL BE INCLUDED. | | | | | | SIZING FOR THRU THE WALL TRANSFER | | | GRILLES SHALL USE 50 SQUARE INCHES TO | | | 100 CFM OF SUPPLY AIR WITH UNRESTRICTED | | | 1" DOOR UNDERCUT. | | | | | | DUCTS SHALL NOT BE INSTALLED IN OR | | | WITHIN 6" OF THE GROUND PER 2001 FBC(M) | | | 603.12. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|