Plan Review Notes
Plan Review Notes For Permit 03092021
Permit Number 03092021
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.PLEASE SEE FAC
 FOR INFORMATION REQUIRED (FIRM LICENSE
 NUMBER).
  
 2} PLEASE REVISE THE RISER DIAGRAM TO
 INCLUDE ANY EXISTING PANELS AND SUPPLY
 SCHEDULES OF SAME.ALL EQUIPMENT IN
 CALCS NOT SHOWN ON NEW PANEL.
  
 3} NOTE THE #3 FEEDERS TO THE 200 AMP
 DISCONNECT ARE INCORRECT FOR THE LOAD
 SERVED PER 310.15(B)(6),OR 310.16.ALSO
 NOTE THERE IS NO NEUTRAL INDICATED,AND
 THE #4 GROUND TO THE FIRST MEANS OF
 DISCONNECT PROVIDES A PARALLEL PATH
 WITH THE NEUTRAL(IF THERE WAS ONE). SEE
 250.6(B).
  
 4} THE 200 AMP DISCONNECT ON THE RISER
 SHOWS TWO SETS OF 200 AMP FUSES,THREE
 PHASE? SEE COMMENT #2.
  
 5} SHEET E.1 SHOWS A METER AND TWO
 DISCONNECTS,PLEASE LABEL INTENDED USE.
  
 6} PLEASE CONFIRM THE SERVICE BEING
 THREE PHASE AND THAT A HIGH LEG EXISTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718