Text |
| 2003-10-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHTS A/060 & A/061 DEMO NOTE #11, ALL |
| | CAPPED PLUMBING LINES SHALL BE INSPECTED |
| | PRIOR TO COVERING. |
| | 2) SHT A/100 WOMENS TOILET ROOM #027, |
| | WHERE 6 OR MORE STALLS ARE PROVIDED, IN |
| | ADDITION TO THE STALL COMPLYING WITH 11- |
| | 4.17.3, AT LEAST ONE STALL 36" WIDE WITH |
| | AN OUTWARD SWINGING, SELF-CLOSING DOOR |
| | AND PARALLEL GRAAB BARS COMPLYING WITH |
| | FIG. 30(D) AND 11-4.16 SHALL BE PROVIDED |
| | 3) SHT K-2 PLUMBING NOTES #2 - CONTACT |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE |
| | FOR SIZE OF GREASE INTERCEPTOR. UTILITY |
| | ORD. #29389-96. (561) 837-4074 |
| | 4) PLANS SHALL BE ROUTED TO THE DEPART- |
| | MENT OF BUSINESS REGULATION HOTEL AND |
| | RESTAURANT DIVISION FOR REVIEW PRIOR TO |
| | SUBMITTING TO CITY FOR PLAN REVIEW. ALL |
| | REVIEW/WORK SHEETS SHALL ACCOMPANY THE |
| | PLANS FOR REVIEW. (954) 958-5520 |
| | SECTION 101.4.7 |
| | 5) SHTS MP060, MP061, & MP100 ALL CAPPED |
| | PLUMBING LINES TO BE INSPECTED PRIOR TO |
| | COVERING. |
| | 6) SHT MP 301 ALL WATER RISER DIAGRAMS, |
| | ALL WATER HAMMER ARRESTORS SHALL BE LO- |
| | CATED NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN. PDI- |
| | WH 201 AND MANUF. INSTALLATION INSTRUCT- |
| | IONS. UNLESS BOTH WASH MACHINES ARE ON A |
| | COMMON DROP, BOTH WASH MACHINES WILL RE- |
| | QUIRE A WATER HAMMER ARRESTOR. |
| | |
| | REVIEW BY KEN STEVENS |