| Plan Review Notes For Permit 03092017 |
| Permit Number |
03092017 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03092017PHASE 1B | | | ADD: 630 CLEARWATER PARK DR | | | 8TH & 7TH FLOORS | | | CONT: WHITING-TURNER CONT CO | | | TEL: (954)776-0880 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1)1606.1.4(1) IN WIND BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IN BUILDINGS SHALL BE | | | ASSUMED TO BE OPENINGS UNLESS SUCH | | | GLAZING IS IMPACT RESISTANT OR PROTECTED | | | WITH AN IMPACT RESISTANT COVERING MEET- | | | ING THE REQUIREMENTS OF SSTD 12, ASTM | | | E 1886 AND ASTM E 1996 OR MIAMI-DADE. | | | | | | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT | | | OF GRADE SHALL MEET THE REQUIREMENTS OF | | | LARGE MISSLE TEST. | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORT, SBCCI OR DADE COUNTY | | | REPORT ARE ACCEPTED. | | | MISSING ALL PRODUCT APPROVALS!!!!!!!!!! | | | | | | 2)EFIS SYSTEM EXTERIOR WALL COVERINGS: | | | ARE TO COMPLY WITH 2603.(1-7) | | | (1) PROVIDING TESTING ON ACCORDANCE WITH | | | ASTM E 119 | | | (2) THERMAL BARRIER | | | (3) POTENIAL HEAT | | | (4) FLAME SPREAD/ SMOKE DEVELOPMENT | | | (5) TEST STANDARD | | | (6) LABEL REQUIRED | | | (7) IGNITION | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|