Plan Review Notes
Plan Review Notes For Permit 03092007
Permit Number 03092007
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-08 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ALL NEW EQUIPMENT/ INCLUDING EXIST-
 -ING. PLEASE INCLUDE THE SIZE IF EXIST-
 -ING SERVICE.
  
 2)NOTE: PLEASE INCLUDE HEAT PUMP WIRING
 ETC ON WIRING DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]