Plan Review Notes
Plan Review Notes For Permit 03091886
Permit Number 03091886
Review Stop B
Sequence Number 2
Notes
Date Text
2003-11-19 00:00:00UNSAT
  
 1) SUBMIT A COPY OF THE PAID RECIEPT FOR
 THE COUNTY IMPACT FEES.
  
 2) PLAN SHEETS A1, A6 AND A7 CONTAIN
 STRUCTURAL INFORMATION AND ARE REQUIRED
 TO BE SIGNED BY THE ENGINEER. THE
 ENGINEER'S TITLE BLOCK IS REQUIRED TO BE
 ON EACH SHEET THAT HE SIGNS AND SEALS.
 SEE FAC 61G15-23. A COPY IS ATTACHED.
  
 3) THE DOOR FROM THE GARAGE TO THE
 CONDITIONED SPACE IS REQUIRED TO BE
 SOLID CORE OR INSULATED PER FBC CHAPTER
 13.
  
 4) THREE OF THE DETAILS ON SHEET S4 ARE
 NOT LABELED. THE OTHER TWO DETAILS ARE
 LABELED A AND B ON SK INSTEAD OF S4.
  
 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 (2) J BOLTS OR 5/8" EXPANSION BOLTS ON
 THE GARAGE BUCK DETAIL ON A7.
  
 6) SECTION 1 ON S3 SPECIFIES A SIMPSON
 NSTA 18 STRAP. THIS SHOULD BE MSTA 18 AS
 SHOWN IN THE DETAIL ON S4.
  
 7) THE SECOND FLOOR ROOF PLAN CALLS FOR
 AN "L" TRUSS ANCHOR FOR SEVERAL TRUSSES.
 THE ANCHOR SCHEDULE DOES NOT LIST THIS
 ANCHOR. SEE SHEET S2.
  
 8) THE GIRDER TRUSSES ON S2 HAVE A NOTE
 TO SEE DETAIL 3/S4. THIS SHOULD BE 3/S3.
  
 9) CHANGE THE WIND 140 SBC ON S2 TO WIND
 140 FBC.
  
 10) THE MAXIMUM UPLIFT FOR THE SIMPSON
 HETAL 16 IS 1515. PLEASE CORRECT ANCHOR
 SCHEDULE ON S2.
  
 11) CLARIFY THE NAILING INFO ON DETAIL
 1/S3. THE 1-3/4" NAILS 4"OC IS FOR THE
 LATH NOT THE PLYWOOD SHEATHING.
  
 12) LABEL AND TIE DETAILS ON S4 TO THE
 AREAS ON THE PLANS TOP WHICH THEY
 CORRESPOND.
  
 13) SUBMIT PRODUCT APPROVALS FOR THE
 IMPACT RESISTANT FIXED GLASS ARCHTOP
 WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714