| Plan Review Notes For Permit 03091886 |
| Permit Number |
03091886 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-09 00:00:00 | DENIED: | | | 1. PLEASE NOTE, REVISION TO THE 2001 | | | FBC(M) 601.4, EFFECTIVE JUNE 30,2003: | | | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM ITS SERVING & THE | | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. | | | | | | 2. AHU #2 INSTALLED IN THE ATTIC SHALL | | | COMPLY WITH 2001 FBC CHAPTER 13 SUB | | | CHAPTER 610.1.ABC.3.5.2. | | | | | | 3.PLEASE NOTE SHOWER/BATH AREAS SHALL | | | HAVE A WINDOW WITH 3 SQ FT OF OPEN SPACE | | | OR BE MECHANICALLY VENTILATED AS PER | | | 2001 FBC 402.3.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|