2003-10-09 00:00:00DENIED:
 1. PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 2. AHU #2 INSTALLED IN THE ATTIC SHALL
 COMPLY WITH 2001 FBC CHAPTER 13 SUB
 CHAPTER 610.1.ABC.3.5.2.
  
 3.PLEASE NOTE SHOWER/BATH AREAS SHALL
 HAVE A WINDOW WITH 3 SQ FT OF OPEN SPACE
 OR BE MECHANICALLY VENTILATED AS PER
 2001 FBC 402.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.