| Plan Review Notes For Permit 03091886 |
| Permit Number |
03091886 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-08 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | | FS 481. PLEASE INCLUDE ALL INFORMATION | | | ON TITLE BLOCKS AS REQ'D. | | | ARCH'S LICENSE #, FIRM LICENSE #,,, | | | | | | 2)NOTE: PLEASE SEE 210.52 FOR RECEPT | | | SPACING. DINING RM, BR#4, BR#3,, ALSO | | | WITHIN 6' OF DOORS, BR#2 ETC. | | | PLEASE SEE 210.52E FOR MISSING RECEPT | | | IN FRONT OF DWELLING. (2FT WALLS) | | | | | | 3)NOTE: PLEASE SEE THAT A LIGHTING | | | FIXTURE OF SOME TYPE WILL BE REQ'D FOR | | | MEANS OF EGRESS @ STAIRWELL. PLEASE SEE | | | THAT IT IS NOW SHOWN ONNLY AS J-BOX. | | | 210.70, LS 101 5-8 | | | | | | 4)NOTE: PLEASE SEE 250.50 FOR REQ'D | | | FOOTER STEEL ON GROUNDING ELECTRODE | | | SYSTEM. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|