| 2003-11-03 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE ARCHITECT'S TITLE BLOCK IS |
| | REQUIRED TO LIST THE FIRM LICENSE NUMBER |
| | AND THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT PER FAC 61G-16.004. |
| | |
| | 3) SPECIFY IN THE DESIGN PARAMETERS THAT |
| | THE ATTIC LIVE LOAD IS 10 PSF FOR ATTICS |
| | WITHOUT STORAGE AND 30 PSF FOR ATTICS |
| | WITH STORAGE. SEE FBC TABLE 1604.1. |
| | |
| | 4) PLEASE CORRECT NOTE #9 ON A2 AND A3, |
| | WHICH SPECIFIES THAT AHU ARE TO BE |
| | LOCATED IN CONDITIONED SPACE. PLANS SHOW |
| | ONE IN GARAGE AND ONE IN ATTIC. |
| | |
| | 5) NOTES 15 & 16 UNDER DESIGN PARAMETERS |
| | ON A1 SPECIFY STORM PANELS AND THE |
| | WINDOW & DOOR SCHEDULE ON A2 SPECIFIES |
| | IMPACT GLAZING. |
| | |
| | 6) ITEM #5 ON THE DOOR SCHEDULE ON A2 |
| | SPECS. A STORM PANEL FOR THE WOOD FRONT |
| | DOOR WHICH IS NOT INDICATED AS HAVING |
| | ANY GLAZING ON THE PLANS. PLEASE CLARIFY |
| | |
| | 7) SPECIFY THE WIDTH OF THE STAIRS AND |
| | DIMENSIONS OF THE LANDINGS. PROVIDE A |
| | DETAIL INDICATING CONNECTIONS AND |
| | FIREBLOCKING AT THE TOP AND BOTTOM OF |
| | STAIR RUNS. SPECIFY THE MATERIAL USED |
| | FOR FIREBLOCKING. |
| | |
| | 8) SPECIFY THE INTERIOR DOOR SIZES ON |
| | THE PLANS. |
| | |
| | 9) PLEASE REVIEW THE 2ND FLOOR WINDOWS |
| | MARKED (B) WHICH ON A4 ARE NOT DRAWN TO |
| | SCALE. THEY MAY INTERFERE WITH THE ROOF |
| | BELOW. REVISE AS REQUIRED. |
| | |
| | 10) PROVIDE COMPLETE SHOP DRAWINGS AND |
| | DETAILS FOR THE FRONT BALCONY RAILS. |
| | SPECIFY FASTENERS AND ATTACHMENTS. |
| | |
| | 11) REVISE THE DESIGN PRESSURES FOR |
| | EXTERIOR OPENINGS LOCATED IN THE END |
| | ZONES. SEE FBC TABLE 1606.2B. |
| | |
| | 12) REVISE HORIZONTAL WALL LOAD INFORM- |
| | ATION ON A6. THE MAXIMUM HORIZONTAL WALL |
| | LOADS ARE +26.0 AND -19.7. THE INTERNAL |
| | PRESSURE COEFFICENT FOR AN ENCLOSED |
| | STRUCTURE IS + OR - 0.18. SEE FBC TABLE |
| | 1606.2A AND ASCE7-98. |
| | |
| | 13) REVISE THE INFORMATION LISTED FOR |
| | THE SIMPSON SP6 CONNECTOR. REMOVE THE |
| | AVERAGE ULTIMATE UPLIFT VALUE AS IT CAN |
| | NOT BE USED. THE ALLOWABLE UPLIFT LOAD |
| | IS 630#. THIS CONNECTOR REQUIRES (6) 10D |
| | NAILS W/ ONE DRIVEN AT AN ANGLE THROUGH |
| | THE STUD AND INTO THE PLATE. |
| | |
| | 14) INDICATE THE LOCATIONS OF THE 24" |
| | WIDE SIMPSON "STRONG-WALL SHEARWALL" |
| | SEGMENTS ON THE SECOND FLOOR WALL |
| | FRAMING PLAN. |
| | |
| | 15) PROVIDE SECTIONS THAT INDICATE A |
| | CONTINOUS LOAD TRANSFER PATH FOR THE |
| | AREAS OF THE 2ND FLOOR OTHER THAN AT THE |
| | SHEAR WALL SEGMENTS. SPECIFY ALL |
| | CONNECTORS. |
| | |
| | 16) SPECIFY THE SIZE AND MATERIAL FOR |
| | THE FIREBLOCKING AT THE TOP OF THE CBS |
| | WALL. SEE FBC 2305. |
| | |
| | 17) REVISE THE VALUES FOR THE USP TA20R |
| | CONNECTOR LISTED ON THE SECTION ON A6. |
| | THE MAXIMUM UPLIFT VALUE IS 1205# WITH |
| | NO INCREASE IN THE STEEL CALCULATIONS. |
| | 1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS.INCREASE IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | |
| | 18) REVISE THE CONNECTOR SCHEDULE ON A7. |
| | THE ULTIMATE LOADS (TEST LOADS) ARE NOT |
| | ALLOWED TO BE USED FOR DESIGN. USE THE |
| | ALLOWABLE LOADS. SPECIFY VALUES THAT DO |
| | NOT INCLUDE A STRESS INCREASE ON THE |
| | STEEL CALCULATIONS. SEE 2003 USP OR 2002 |
| | SIMPSON HIGH WIND CONST. CATALOGS. |
| | |
| | 19) REVISE THE GUARDRAIL DETAIL ON A6. |
| | THE SPACE BELO THE BOTTOM RAIL MUST |
| | REJECT A 2" SPHERE. FBC 1015 |
| | |
| | 20) THE NOTE ON A7 SPECIFIES 48" BETWEEN |
| | VERTICAL MASONRY WALL REINFORCEMENT AND |
| | THIS CONFLICTS WITH THE FOUNDATION PLAN |
| | ON S1. |
| | |
| | 21) CLARIFY THE UNEQUAL SPACING OF THE |
| | FASTENERS FOR THE GARAGE DOOR BUCK ON A7 |
| | MAKE SURE THAT THIS CORRESPONDS TO THE |
| | PRODUCT APPROVAL FOR THE GARAGE DOOR. |
| | |
| | 22) REVISE THE VENTING NOTES ON A8 TO |
| | NET FREE VENT AREA AND CEILING AREA. |
| | SEE FBC 2309.2.1. |
| | |
| | 23) PROVIDE AN INTERIOR BEARING WALL |
| | SECTION. SPECIFY ALL CONNECTORS, SIZE & |
| | SPACING OF FRAMING MEMBERS, ETC. |
| | |
| | 24) SPECIFY THE SIZE AND REINFORCEMENT |
| | AT THE ISOLATED PAD AT THE COVERED REAR |
| | PORCH. |
| | |
| | 25) THE F1 FOOTER MARKS ARE IN THE WRONG |
| | LOCATION AT THE COVERED REAR PORCH AREA |
| | ON S1. |
| | |
| | 26) REVISE THE COLUMN DETAIL ON S1. SEE |
| | NOTES ON THE PLANS. THE UPLIFT VALUES |
| | ARE INCORRECT, CONNECTORS FOR WRONG POST |
| | DIMENSIONS, POST CAP TO RECEIVE BEAMS AT |
| | 90 DEGREES REQUIRED, ETC. |
| | |
| | 27) SPECIFY CONNECTORS FOR THE 2 X 12 |
| | BEAMS AT THE MASONRY WALLS. |
| | |
| | 28) SEVERAL OF THE REINFORCED BLOCK |
| | COLUMNS AT THE FRONT ENTRY AREA ARE NOT |
| | MARKED ON THE FOUNDATION PLAN ON S1. |
| | |
| | 29) THE LOWER ROOF PLAN ON S2 DOES NOT |
| | CORRESPOND WITH THE FOUNDATION PLAN. |
| | PLEASE REVISE. |
| | |
| | 29) CLARIFY AND PROVIDE DETAIL/SECTION |
| | OF THE LOWER ROOF AT THE LIVING ROOM. |
| | IS IT CANTILEVERED OR SUPPORTED BY A |
| | BEAM? |
| | |
| | 30) PROVIDE A SECTION/DETAIL OF THE |
| | BALCONY. |
| | |
| | 31) PROVIDE A FLOOR FRAMING PLAN FOR THE |
| | SECOND FLOOR. INDICATE THE LOCATION OF |
| | GIRDERS SUPPORTING WALLS. SPECIFY ALL |
| | CONNECTORS. |
| | |
| | 32) INDICATE THE LOCATION OF THE FLOOR/ |
| | CEILING ASSEMBLY DRAFTSTOPPING ON THE |
| | FLOOR FRAMING PLAN AND SPECIFY THE |
| | MATERIALS THAT WILL BE USED. |
| | SEE FBC 2305.2.2 AND 2305.2.6. |
| | |
| | 33) SPECIFY ALL CONNECTORS ON THE ROOF |
| | AND FLOOR FRAMING PLANS AND PROVIDE A |
| | TRUSS ANCHOR SCHEDULE KEYED TO THE PLANS |
| | |
| | 34) PROVIDE A SECTION/DETAIL INDICATING |
| | THE ATTACHMENT OF THE LOWER ROOF TRUSSES |
| | TO THE SECOND FLOOR FRAME WALLS. |
| | SPECIFY CONNECTORS. |
| | |
| | 35) SPECIFY ALL PERMANENT ROOF BRACING. |
| | |
| | 36) PROVIDE A DETAIL INDICATING HOW THE |
| | SECOND FLOOR WOOD FRAME WALLS WILL BE |
| | ANCHORED TO THE FLOOR TRUSSES TO PROVIDE |
| | A CONTINOUS LOAD PATH. |
| | |
| | 37) PROVIDE A DETAIL INDICATING HOW THE |
| | THREE WINDOWS AT BEDROOM #1 ON THE FIRST |
| | FLOOR ARE TO BE CONNECTED TOGETHER. THE |
| | SPACE BETWEEN THEM IS TOO LARGE FOR A |
| | MULLION AND NO COLUMNS ARE SHOWN ON THE |
| | PLANS AT THIS LOCATION. |
| | |
| | 38) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE FRONT AND SIDE DOORS IS NOT LEGIBLE. |
| | THE FRONT DOOR INDICATED ON THE PLANS |
| | DOES NOT MATCH THE PRODUCT APPROVAL. |
| | THE DOOR SCHEDULE ON A2 SPECIFIES |
| | ALUMINUM FRAMES. PLEASE REVISE SCHEDULE |
| | TO MATCH PRODUCT APPROVALS. THE DESIGN |
| | PRESSURES LISTED ON THE PRODUCT APPROVAL |
| | FOR THE FRONT DOOR +49 AND -60 DO NOT |
| | MEET THE REQUIRED DESIGN PRESSURES THAT |
| | ARE LISTED ON THE PLANS. |
| | |
| | 39) CLARIFY WHY STORM PANELS HAVE BEEN |
| | SPECIFIED FOR THE FRONT AND SIDE DOORS. |
| | THE PRODUCT APPROVAL SUBMITTED ONLY |
| | REQUIRES STORM PANELS WHEN THESE DOORS |
| | HAVE SIDELITES AND THE PLANS DO NOT |
| | SHOW ANY GLAZING FOR THESE DOORS. |
| | |
| | 40) SUBMIT THE APPROVED DRAWINGS FOR THE |
| | GARAGE DOORS. THE DRAWINGS ATTACHED TO |
| | THE SUBMITTED PRODUCT APPROVALS ARE FOR |
| | STORM PANELS. |
| | |
| | 41) SEE ADDITIONAL REVIEW NOTES ON THE |
| | PLANS. |
| | |
| | 42) THE BUILDING VALUATION WAS UPDATED |
| | TO $ 302,170. ADDITIONAL FEES WILL BE |
| | ADDED TO REFLECT THIS REVISED VALUE. |
| | |