| Notes |
| Date |
Text |
| 2005-06-18 00:00:00 | 1.SECONDARY ROOF DRAIN SYSTEMS SHALL BE | | | SEPARATE FROM PRIMARY DRAINS SEE FBC | | | PLUMBING SEC. 1107.1 AND SIZE PER. | | | SEC.1107.3. | | | 2.PLEASE SHOW AREA TO BE DRAINED, SQ.FT. | | | OF DECK AND OTHER RUN OFF FROM OTHER | | | ROOF SECTIONS. SIZE ROOF DRAIN AND RAIN | | | WATER LEADER PER TABLE 1106.2 AND 1106.3 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|