| Plan Review Notes For Permit 03091830 |
| Permit Number |
03091830 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-12-18 00:00:00 | DENIED: | | | | | | 1.FORM 600C SUBMITTED FOR THE ADDITION | | | TO THE EXISTING RESIDENCE DOES INDICATES | | | 561 SQ FT.THE MANUAL J REFLECTS SYSTEM | | | 1 INDICATES THE TOTAL EQUIPMENT LOAD | | | WILL BE APPROXIMATELY 2 TONS.THE PLAN | | | INDICATES A 4 TON UNIT.IF THE 4 TON | | | IS EXISTING PLEASE INDICATE THIS ON THE | | | FORM 600C.SHOULD SYSTEM 1 BE A NEW | | | INSTALLATION, PLEASE PROVIDE ENERGY & | | | MANUAL J CALCULATIONS BASED UPON METHOD | | | A OF THE 2001 FBC CHAPTER 13 SUBCHAPTER | | | 600. | | | | | | 2.THE ENERGY CALCULATIONS FOR THE | | | ACCESSORY BUILDING INDICATES 387 SQ FT | | | OF CONDITIONED SPACE, REQUIRING A 2 TON | | | UNIT.THE EQUIPMENT SCHEDULE ON M-1 | | | SHOWS A 3 TON UNIT.PLEASE REVISE PLAN | | | TO MATCH THE ENERGY CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|