| 2003-11-08 00:00:00 | ****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.CALL 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4.)SEE PREVIOUS LIST, ITEM #5, THE |
| | SOILS REPORT IS REQUIRED TO BE SEALED, |
| | BOTH COPIES, FS471.025. |
| | |
| | 5.)SEE PREVIOUS LIST, THE SEPTIC TANK |
| | REMOVAL REQUIRES A PERMIT FROM PALM |
| | BEACH COUNTY HEALTH DEPARTMENT,233-5386. |
| | PROVIDE A COPY OF THE PERMIT. |
| | |
| | 6.)THE ENERGY CALCS ARE NO LONGER |
| | CORRECT AS THE A/C AREA HAS CHANGED. |
| | AFTER CORRECTION OF THE ENERGY CALCS, |
| | SIGN THE OWNER/AGENT LINE FBC13-101.2 |
| | BEFORE RESUBMITTAL. |
| | |
| | 7.)SEE PREVIOUS LIST, ITEM #10, THE |
| | AREA (2ND FLOOR OF ACCESSORY STRUCTURE) |
| | REFERRED TO AS AN "ATTIC" IS NOT AN |
| | ATTIC PER FBC13-202, DEFINITIONS. |
| | ALSO THIS AREA IS STILL SHOWN AS A/C |
| | AREA (AREA CALCULATIONS).AS DISCUSSED, |
| | IF THIS IS HABITABLE SPACE A STAIR OR |
| | RAMP IS REQUIRED FOR CHANGES IN LEVEL |
| | OF MEANS OF EGRESS FBC1003.2.7.IF THIS |
| | IS AN ATTIC, MUST MEET THE DEFINITION |
| | OF AN ATTIC (UNCONDITIONED VENTILATED |
| | SPACE).VENTILATION IS TO COMPLY WITH |
| | FBC2309.7, PROVIDE CALCULATIONS. |
| | |
| | 8.)THE FIRESTOP SHOWN ON THE WALL |
| | SECTIONS DOES NOT COMPLY WITH FBC705.3. |
| | SEE ATTACHED. |
| | |
| | 9.)AS DISCUSSED, THE PERMIT CAN BE |
| | ISSUED WITH A PROVISO THAT THE 5371 |
| | WINDOW AT THE SITTING ROOM PRODUCT |
| | APPROVAL BE SUBMITTED LATER.HOWEVER, |
| | ITEMS #13 AND #14 WERE NOT ADDRESSED; |
| | TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | FIXED GLASS WINDOW AND FRENCH DOOR |
| | SIDELITES AND MULLIONS. |
| | |
| | 10.) SHEET S2, TRUSS BOTTOM CHORD LIVE |
| | LOAD IS REQUIRED TO BE 10PSF FBC TABLE |
| | 1604.1 (RES, DWELLINGS, ATTICS WITHOUT |
| | STORAGE). |
| | |
| | 11.) THE ARCHITECTS SEAL IS TO BE DATED, |
| | FS481.221(1)(A). |
| | |
| | 12.) PROVIDE DIMENSIONS FOR THE STAIRS. |
| | THE DIMENSIONS SHOULD COMPLY WITH FBC |
| | 1007.3.1 (TWO RISERS AND A TREAD NOT |
| | LESS THAN 24", NO MORE THAN 25"). |
| | |
| | 13.) IF THE SECOND FLOOR OF THE |
| | ACCESSORY BUILDING IS AN ATTIC, IT MUST |
| | HAVE ATTIC VENTILATION TO COMPLY WITH |
| | FBC2309.7, PROVIDE CALCULATIONS. |
| | |
| | 14.)A8, SECTION 1, ANCHOR BOLTS AND |
| | TAP CONS ARE SPECIFIED WITH A DIAMETER |
| | BUT NO LENGTH OR EMBEDMENT REQUIREMENT. |
| | SPECIFY LENGTH IN ALL DETAILS. |
| | |
| | 15.)I WAS UNABLE TO FIND THE LUS44 |
| | INVERTED APPLICATION IN THE SIMPSON |
| | CATALOG.CONFIRM WITH THE MANUFACTURER |
| | (SPEC SHEET OR LETTER) THAT THIS IS A |
| | SUITABLE APPLICATION FOR THIS PRODUCT. |
| | |
| | 16.) WHEN RESUBMITTING, REPLACE ONLY |
| | SHEETS WHICH HAVE BEEN REVISED.SUBMIT |
| | OLD SHEETS SEPARATELY.ALSO SUBMIT THE |
| | OLD SHEETS FROM THE FIRST REVIEW. |