| Plan Review Notes For Permit 03091790 |
| Permit Number |
03091790 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-01 00:00:00 | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION FOR REVIEW TO DETERMINE CODE | | | COMPLIANCE.RESUBMIT SAME. | | | | | | 1} A FLOOR PLAN SHOWING THE LOCATION OF | | | THE NEW EQUIPMENT,AND THE FEEDER SIZE | | | AND OVERCURRENT PROTECTION LOCATION AND | | | SIZE. | | | | | | 2} A DIAGRAM SHOWING HOW THE NEW PANEL | | | IS BEING FED. | | | | | | 3} RATING OF THE NEW PANEL. | | | | | | 4} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110.9. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|