 PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW TO DETERMINE CODE
 COMPLIANCE.RESUBMIT SAME.
  
 1} A FLOOR PLAN SHOWING THE LOCATION OF
 THE NEW EQUIPMENT,AND THE FEEDER SIZE
 AND OVERCURRENT PROTECTION LOCATION AND
 SIZE.
  
 2} A DIAGRAM SHOWING HOW THE NEW PANEL
 IS BEING FED.
  
 3} RATING OF THE NEW PANEL.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  